Installing the Refrigerant Pipe Work (Continued)
22
E-
FJM RD040MHXCA_IM_00000_E_2.23.10.indd 22
NIT
Selecting Additional Refrigerant Charge
Basic charge
The basic amount of refrigerant for outdoor unit charged in factory is :
Outdoor unit (Series)
Charge additional refrigerant according to the total length of the pipe.
Refrigerant Charging
Additional charging
Additional Refrigerant calculation only related with liquid pipe length
Basic refrigerant for outdoor unit already has been charged
Additional charge calculation = (Sum of total length(m) of Φ9.52)x50g +
ex) a(Φ9.52)=40m(131.2ft), b+c+d(Φ9.52)=15m(49.2ft),e+f+g(Φ6.35)=15m(49.2ft)
Factory charge(kg(lb))
RD040MHXCA
RD050MHXCA
Depends on the total length of the liquid side pipe.
Additional Charge (g) = {(L1(m)x20(g/m)) + (L2(m)x50(g/m))}
(oz) = {(L1(ft)x0.215(oz/ft)) + (L2(ft)x0.54(oz/ft))}
L1(m(ft)): Total length of liquid pipe Ø 6.35(Ø1/4)
L2(m(ft)): Total length of liquid pipe Ø 9.52(Ø3/8)
(Sum of total length(m) of Φ6.35)x20g
= (Sum of total length(ft) of Φ9.52)x0.54oz +
(Sum of total length(ft) of Φ6.35)x0.215oz
Additional charge = 55mx50g + 15mx20g = 3050g
= 180.4ftx0.54oz + 49.2ftx0.215oz = 108oz