Function
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Heating curve slope
Heating curve displacement
Heating curve adaption
Off | On
Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
Flow temp setpoint room stat
Delay heat request
Room influence
Room temp limitation
Boost heating
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
Optimum start control max
Optimum stop control max
Reduced setp increase start
Reduced setp increase end
Continuous pump operation
No | Yes
Overtemp prot pump circuit
Off | On
Mixing valve boost
Actuator running time
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
Floor curing setp manually
Floor curing setp current
Floor curing day current
Excess heat draw
Off | Heating mode | Always
With buffer storage tank
No | Yes
With prim contr/system pump
No | Yes
Pump speed reduction
Operating level | Characteristic
Pump speed min
Pump speed max
Curve readj at 50% speed
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
Programming
Prog.
Standard value
1)
Level
no.
1010
Eu
20.0°C
1012
Eu
18.0°C
1014
Eu
10.0°C
1020
Eu
1.50
1021
E
0.0°C
1026
E
Off
1030
Eu
20°C
1032
E
- 0°C
1040
E
8°C
1041
E
80°C
1042
E
- - -°C
1046
E
0s
1050
C
- - - %
1060
E
0.5°C
1070
E
- - -°C
1080
E
Down to reduced set-
point
1090
E
0 min
1091
E
0 min
1100
E
- - -°C
1101
E
-15°C
1109
E
No
1120
E
Off
1130
E
5°C
1134
E
120 s
1150
E
Off
1151
E
25°C
1155
E
- - -°C
1156
E
0°C
1161
E
Heating mode
1170
E
Yes
1172
E
Yes
1180
E
Characteristic
1182
C
10 %
1183
C
100 %
1188
E
10 %
57