Premierlink Controller; Optional Economi$Er2 - Carrier 48TM004-007 Installation, Start-Up And Service Instructions Manual

Single-package rooftop heating/cooling units
Table of Contents

Advertisement

PREMIERLINK™ CONTROL — The PremierLink control-
ler is compatible with the Carrier Comfort Network (CCN).
This control is designed to allow users the access and ability to
change factory-defined settings, thus expanding the function of
the standard unit control board. Carrier's diagnostic standard
tier display tools such as Navigator or Scrolling Marquee can
be used with the PremierLink controller.
The PremierLink controller (see Fig. 16) requires the use of
a Carrier electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is necessary for
broadcast of time of day functions (occupied/unoccupied).
Refer to Fig. 17. No sensors are supplied with the field-
mounted PremierLink control. The factory-installed Premier-
Link control includes only the supply-air sensor (SAT) as
standard. The PremierLink control may be mounted in the con-
trol panel or an area below the control panel. If used with the
EconoMi$er2 the standard OAT (outdoor-air temperature) sen-
sor and Compressor Lockout Sensor supplied with the
EconoMi$er2 will need to be changed to the PremierLink com-
patible sensors. Refer to the PremierLink control and
EconoMi$er2 Installation, Start-up and Configuration Instruc-
tions for more information.
OPTIONAL ECONOMI$ER2 — See Fig. 18 for Econo-
Mi$er2 component locations.
NOTE: These instructions are for installing the optional
EconoMi$er2 only. Refer to the accessory EconoMi$er2
installation instructions when field installing an EconoMi$er2
accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. See
Fig. 19.
2. The box with the EconoMi$er2 hood components is
shipped in the compartment behind the EconoMi$er2. In
order to remove the box, the EconoMi$er2 controller
must be temporarily moved. This step does not need to be
performed on an EconoMi$er2 with 4 to 20 mA control
as there is no controller. The entire EconoMi$er2 does not
have to be removed to retrieve the hood box. The
EconoMi$er2 controller is mounted on top of the
EconoMi$er2 in the position shown in Fig. 18.
IMPORTANT: If the power exhaust accessory is to be
installed on the unit, the hood shipped with the unit
will not be used and must be discarded. Save the alu-
minum filter for use in the power exhaust.
3. The indoor coil access panel will be used as the top of the
4. Swing out indoor coil access panel and insert the hood
5. Remove the shipping tape holding the EconoMi$er2
6. Insert the hood divider between the hood sides. See
7. Open the filter clips which are located underneath the
8. Caulk the ends of the joint between the unit side panel
9. Replace the filter access panel.
10. Install all EconoMi$er2 accessories. EconoMi$er2 wiring
Fig. 16 — PremierLink Controller
16
a. Remove the screws holding the controller bracket
in place. Save screws. Temporarily lower the con-
troller. See Fig. 20. Do not disconnect the control-
ler wiring.
b. Remove the screw holding the hood box bracket to
the top of the EconoMi$er2. Slide the hood box out
of the unit. See Fig. 20 and 21.
c. Reinstall the EconoMi$er2 controller in its original
position using the screws saved in Step 2a. Tighten
screws.
hood. Remove the screws along the bottom of the indoor
coil access panel. See Fig. 22.
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws pro-
vided to attach the hood sides to the unit. See Fig. 23.
barometric relief damper in place.
Fig. 23 and 24. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the bot-
tom filter rack for the aluminum filter.
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. See Fig. 24.
and the hood top. See Fig. See Fig. 22.
is shown in Fig. 25 and 26.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48tf004-007

Table of Contents