Start-Up; Compressor Rotation; Main Burners; Altitude Compensation—Standard And No Nox Units - Carrier 48TM004-007 Installation, Start-Up And Service Instructions Manual

Single-package rooftop heating/cooling units
Table of Contents

Advertisement

START-UP

Unit Preparation —
Make sure that unit has been
installed in accordance with these installation instructions and
applicable codes.
Return-Air Filters —
Make sure correct filters are
installed in filter tracks. See Tables 1A and 1B. Do not operate
unit without return-air filters.
Compressor Mounting —
spring mounted. Do not loosen or remove compressor hold-
down bolts.
Internal Wiring —
Check all electrical connections in
unit control boxes. Tighten as required.
Gas Piping —
Check gas piping for leaks.
Disconnect gas piping from unit when leak
testing at pressure greater than
sures greater than
valve damage resulting in hazardous condi-
tion. If gas valve is subjected to pressure
greater than
before use. When pressure testing field-
supplied gas piping at pressures of
or less, a unit connected to such piping must
be isolated by manually closing the gas
valve.
Refrigerant Service Ports —
service ports, remove compressor access panel. Each unit sys-
tem has 3 Schrader-type service gage ports: one on the suction
line, one on the liquid line, and one on the compressor dis-
charge line. Be sure that caps on the ports are tight. The
Schrader-type valve on the discharge line is located under the
low-pressure switch. Another valve is located on the discharge
line underneath the high-pressure switch. It is screwed on a
Schrader fitting but there is no Schrader core.
High Flow Valves —
Located on the compressor hot gas
and suction tubes are High Flow Valves. Large black plastic
caps distinguish these valves with O-rings located inside the
caps. These valves cannot be accessed for service in the field.
Ensure the plastic caps are in place and tight or the possibility
of refrigerant leakage could occur.
Compressor Rotation —
compressors, it is important to be certain compressor is rotating
in the proper direction. To determine whether or not compres-
sor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-
sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in
the wrong direction.
2. Turn off power to the unit.
3. Reverse any two of the unit power leads.
Compressors are internally
1
/
psig. Pres-
2
1
/
psig will cause gas
2
1
/
psig, it must be replaced
2
1
/
psig
2
To service refrigerant
On 3-phase units with scroll
4. Reapply power to the compressor.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit makes an elevated level of noise and does not
provide cooling.
Cooling —
Set space thermostat to OFF position. To start
unit, turn on main power supply. Set system selector switch at
COOL position and fan switch at AUTO. position. Adjust ther-
mostat to a setting below room temperature. Compressor starts
on closure of contactor.
Check unit charge. Refer to Service, Refrigerant Charge
section, page 46.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after
30-second delay.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature ex-
ceeds thermostat setting.
Main Burners —
Main burners are factory set and should
require no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. After
ensuring that the unit continues to heat the building, lower the
thermostat setting below room temperature and verify that the
burners and evaporator fan turn off. (Fan will turn off only if
fan selector switch is in the AUTO. position.)
Refer to Tables 30A and 30B for the correct orifice to use at
high altitudes.
Table 30A — Altitude Compensation* —
Standard and No NOx Units
72,000, 74,000 AND
115,000 BTUH
NOMINAL INPUT
ELEVATION
Natural
(ft)
Gas
Orifice
Size†
0-2,000
33
2,000
36
3,000
36
4,000
37
5,000
38
6,000
40
7,000
41
8,000
42
9,000
43
10,000
44
11,000
45
12,000
46
13,000
47
14,000
48
*As the height above sea level increases, there is less oxygen per
cubic foot of air. Therefore, heat input rate should be reduced at
higher altitudes.
†Orifices available through your Carrier distributor.
43
150,000 BTUH
NOMINAL INPUT
Liquid
Natural
Liquid
Propane
Gas
Propane
Orifice
Orifice
Orifice
Size†
Size†
Size†
43
30
37
44
31
39
45
31
40
45
32
41
46
32
42
47
34
43
48
35
43
49
36
44
50
37
45
50
39
46
51
41
47
52
42
48
52
43
49
53
44
50

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48tf004-007

Table of Contents