UNIT SIZE 48TF
FURNACE SECTION
Rollout Switch Cutout
Temp (F)††
Burner Orifice Diameter
(in. ...drill size)
Natural Gas
Liquid Propane
Thermostat Heat Anticipator
Setting (amps)
208/230 v and 575
Stage 1
Stage 2
460 v
Stage 1
Stage 2
Gas Input (Btuh)
Standard Units
(Stage 1/Stage 2)
No NOx Units
Low NOx Units
Efficiency (Steady
State) (%)
Temperature Rise Range
Manifold Pressure (in. wg)
Natural Gas
Liquid Propane
Gas Valve Quantity
Gas Valve Pressure Range
Psig
in. wg
Field Gas Connection
Size (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor
Internal Relief (Differential)
Cutout
Reset (Auto.)
LOSS-OF-CHARGE (LOW-
PRESSURE SWITCH) (psig)
Cutout
Reset (Auto.)
FREEZE PROTECTION
THERMOSTAT (F)
Opens
Closes
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.)
LEGEND
Al
—
Aluminum
Bhp —
Brake Horsepower
Cu
—
Copper
*Evaporator coil fin material/condenser coil fin material. Contact your local
representative for details about coated fins.
†Weight of 14-in. roof curb.
**Single phase/three-phase.
††Rollout switch lockout is manually reset by interrupting power to unit or
resetting thermostat.
Table 1A — Physical Data — 48TF004-007 (cont)
E/F/H/K/M/N004
195
Std
TFD/GII
—
TFE/HII
.113...33
TFF/KII
.113...33
TFL
—
TFM
.102...38
TFN
.102...38
Alt
TFD/GII
—
TFE/HII
.089...43
TFF/KII
.089...43
TFL
—
TFM
.082...45
TFN
.082...45
.14
.14
.14
.14
TFD
—
TFE
—/74,000
TFF***
82,000/115,000
TFGII
—
TFHII
72,000
TFKII
115,000
TFL†††
—
TFM†††
60,000
TFN†††
90,000
80¶
TFD/GII
—
TFE/HII
25-55
TFF/KII
55-85
TFL
—
TFM
20-50
TFN
30-65
Std
3.5
Alt
3.5
1
0.180-0.487
5.0-13.5
1
/
2
D/E/F/G/H/K/L/M/N005 D/E/F/G/H/K/L/M/N006
195
.113...33
.113...33
.129...30
.102...38
.102...38
.116...32
.089...43
.089...43
.104...37
.082...45
.082...45
.094...42
.14
.14
.14
.14
—/74,000
—/115,000
120,000/150,000
72,000
115,000
150,000
60,000
90,000
120,000
80
25-55
35-65
50-80
20-50
30-60
40-70
3.5
3.5
1
0.180-0.487
5.0-13.5
1
/
2
450 ± 50
428
320
7 ± 3
22 ± 7
30 ± 5
45 ± 5
Cleanable
1...20 x 24 x 1
Throwaway
2...16 x 25 x 2
||48TFG, TFH, and TFK units are California compliant three-phase high heat
models.
***Three-phase standard high heat models have heating input values as
shown. Single-phase standard high heat models have one-stage heating
with heating input values as follows:
48TFF004 — 115,000 Btuh
48TFF005,006 — 150,000 Btuh
†††California SCAQMD compliant Low NO
ucts that are controlled to 40 nanograms per joule or less.
¶Steady State Efficiency is 80% on all units except 48TFK004, which is
81%.
NOTE: High-static motor not available on single-phase units.
6
D/E/F007
195
195
.113...33
.113...33
.113...33
.113...33
.129...30
.129...30
.102...38
—
.102...38
—
.116...32
—
.089...43
.089...43
.089...43
.089...43
.104...37
.104...37
.082...45
—
.082...45
—
.094...42
—
.14
.14
.14
.14
.14
.14
.14
.14
—/74,000
—/74,000
—/115,000
—/115,000
120,000/150,000
120,000/150,000
72,000
—
115,000
—
150,000
—
60,000
—
90,000
—
120,000
—
80
80
25-55
25-55
35-65
35-65
50-80
50-80
20-50
—
30-60
—
40-70
—
3.5
3.5
3.5
3.5
1
1
0.180-0.487
0.180-0.487
5.0-13.5
5.0-13.5
1
/
1
/
2
2
500 ± 50
428
320
models have combustion prod-
x