SECTION III: PRE-INSTALLATION (cont.)
LOCATION (cont.)
For ease of access and proper maintenance, the clearances in Figure 3 are strongly recommended.
GAS SUPPLY LINE
Prior to installation, contact your local gas utility to confirm that sufficient gas service is available
for the water heater. The gas meter must have adequate capacity to supply the rated maximum gas
input of the water heater in addition to other gas fired equipment connected to the meter.
Minimum Gas Supply Pressure
The gas supply must be capable of maintaining a minimum pressure at the inlet of the gas control
during water heater operation at maximum input. The pressure will be lowest at the gas control
during water heater operation (i.e. gas is flowing) at maximum input. At minimum, during
operation at maximum input, the supply pressure at the gas control must be at least 6" W.C.
Refer to Table 3 for gas supply line sizing. The table shows maximum input in thousands of BTU's
per hour for various pipe sizes and lengths. The table assumes gas supply pressures of 14" W.C. or
less and a pressure drop of 0.3" W.C.
Table 3: Gas Supply Line Capacity
Nominal
Internal
Iron Pipe
Diameter
Size
10
(inches)
(inches)
1 1/4
1.380
1,050
1 1/2
1.610
1,600
2
2.067
3,050
2 1/2
2.469
4,800
3
3.068
8,500
4
4.026
17,500 12,000
At minimum, use 1-1/4" gas supply pipe for models OT300N(-A) and OT400N(-A).
For model OT500N(-A), use a minimum of 1-1/2" pipe.
Maximum Gas Supply Pressure
The gas supply pressure shall never be greater than 14" W.C. Pressures greater than 14" W.C. may
damage the gas control which could cause a fire or explosion.
Refer to Section IV: Installation / Gas Connections for further installation instructions.
Figure 3: Recommended Minimum Access Clearances
20
30
40
50
730
590
500
440
1,100
890
760
670
2,100
1,650
1,450
1,270
3,300
2,700
2,300
2,000
5,900
4,700
4,100
3,600
9,700
8,300
7,400
Length of Pipe (feet)
60
70
80
90
400
370
350
320
610
560
530
490
1,150
1,050
990
930
1,850
1,700
1,600
1,500
3,250
3,000
2,800
2,600
6,800
6,200
5,800
5,400
100
125
150
175
305
275
250
225
460
410
380
350
870
780
710
650
1,400
1,250
1,130
1,050
2,500
2,200
2,000
1,850
5,100
4,500
4,100
3,800
200
210
320
610
980
1,700
3,500
Page 9