SECTION VII: TROUBLESHOOTING (cont.)
Table 12 shows a list of lockout error codes. A lockout code will be visible on the control
display in the form of a code (letter "A" followed by a number) and a short message. Lockout
errors require a manual reset to resume operation after the root cause of the problem has been
solved. To manually reset the control, press the "i" button on the user interface.
Table 12: Lockout Error Codes
Code
Error Message
EXTND BLOCKING
A00
ERROR
A01
IGNITION LOCKOUT
A05
GV RELAY ERROR
A06
SAFETY RELAY ERROR
A09, A11, A13,
RAM, X!RAM, STATE,
A14
OR ROM ERRORS
A10, A12
E2PROM ERRORS
AIR PROVING SW
A15
ERROR
A16
15MS XRL ERROR
AIR PROVING SW
A17
ERROR
A19, A22, A23,
various software
A27, A28, A29,
errors
A30
A20
FLAME ERROR 2
A21
FLAME ERROR 1
A24
FLAME FAIL LOCKOUT
A36
BLOCKED VENT
A38
LOW GAS PRESSURE
LOCKOUT ERRORS
Description:
A blocking error has been present for more than 20 hours in a row.
Causes & Actions:
Investigate the blocking error that caused the lockout.
Description:
There have been three unsuccessful ignition attempts in a row.
Dirty or faulty flame rod ! see manual.
Damaged or worn hot surface igniter ! see manual.
Causes & Actions:
Faulty or loose wiring ! check wiring and connections to flame rod, hot
surface igniter, gas valve and blower.
Improper venting or restricted inlet/outlet ! see manual.
Description:
A failure was detected in the gas valve relay in the main control.
Causes & Actions:
Contact a qualified agency to inspect the control.
Description:
A failure was detected in the Safety Relay in the main operating control.
Causes & Actions:
Contact a qualified agency to inspect the control.
Description:
Various internal software errors.
Causes & Actions:
Contact a qualified agency to inspect the control.
Description:
Various errors caused by E2PROM file (i.e. software error).
Causes & Actions:
Contact a qualified agency to inspect the control.
Description:
The air proving switch is not opening when the blower is OFF.
Short in the wiring ! check the two pink wires.
Causes & Actions:
Excessive wind or room draft is creating negative pressure.
Description:
Internal software error.
Causes & Actions:
Contact a qualified agency to inspect the control.
Description:
The air proving switch is not closing when the blower is ON.
Switch openings are blocked ! inspect switch and tubing.
Causes & Actions:
Loose or damaged wiring ! inspect pink wires and connections.
Blower is not turning on when energized by the control.
Description:
Internal software error.
Causes & Actions:
Contact a qualified agency to inspect the control.
Description:
The flame is still present 10 seconds after closing the gas valve.
Causes & Actions:
The gas valve is not closing properly ! contact a qualified agency.
Description:
A flame is detected before ignition.
Causes & Actions:
Contact a qualified agency to inspect the controls.
Description:
Flame signal has been lost ten times during one demand.
Dirty or faulty flame rod ! see manual.
Causes & Actions:
Faulty or loose wiring to gas valve ! check wiring and connections.
Description:
Blocked vent error occurs 3 times in a 10 minute period.
Causes & Actions:
See blocking error E36.
Description:
Low gas pressure error occurs 3 times in a 10 minute period.
Causes & Actions:
See blocking error E38.
Description & Possible Causes