Timer and Counter Instructions
Programming
1, 2, 3...
Unit
CPU
Analog Timer Unit
All four time's are used. Times for two of them are adjusted on the variable
resistors provided on the Analog Timer Unit. The other two times are ad-
justed using external resistors. These adjustments are made as follows. Re-
fer to the Analog Timer Unit Installation Guide for hardware details.
Timer
SV
T
Approx. 0.6 s
0
T
Approx. 3 s
1
T
Approx. 2.6 s
2
T
Approx. 8 min
3
The following program sections are used to set up the required data and pro-
duce outputs from the four timers. The first section moves E400 into IR 06 to
set the desired ranges (see table above). The second program section
achieves the following operation.
1.
IR 0500 is turned ON approximately 0.6 seconds after IR 0002 turns ON
as the result of the action of T
2.
IR 0501 is turned ON approximately 3 seconds after IR 0003 turns ON
as the result of the action of T
3.
IR 0502 is turned ON approximately 20 seconds after IR 0004 turns ON
as the result of the action of T
4.
IR 0503 is turned ON approximately 8 minutes after IR 0004 turns ON
as the result of the action of T
5.
T
and T
are made inoperative if IR 0015 is turned ON.
2
3
First Scan Flag
1815
MOV(21)
15
1
Input word
00
02
Range
0.1 to 1 s
1 to 10 s
10 to 60 s
1 to 10 min
.
0
.
1
.
2
.
3
#E400
06
Content of IR O6 after MOV(21)
14
13
12
11
10
09
08
1
1
0
0
1
0
0
Range settings
Section 5–11
Output word
01
03
Resistor adjustment
6/10th turn clockwise
3/10th turn clockwise
2/10th turn clockwise
8/10th turn clockwise
07
06
05
04
03
02
01
00
0
0
0
0
0
0
0
0
63

Hide quick links: