Condenser temperature alarm delay: (0 to 255min) time interval between the detection of an alarm condition at the
condenser and the relative alarm signalling.
Condenser temperature alarm exclusion during start-up: (0 to 720min, resolution 10min).
Compressor off when a low temperature alarm of the condenser is active:
Compressor off when an high temperature alarm of the condenser is active:
Temperature set point change during the Energy Saving cycle: (-30.0 to 30.0°C or -54 to 54°F) sets the deviation
from the normal set point during the Energy Saving cycle.
ON / OFF key enabling:
Buzzer enabling:
Parameter table: read only – for factory use.
Software release: read only – shows the software release.
Evaporator probe: shows the current temperature sensed by the evaporator probe.
Third probe temperature: shows the current temperature sensed by the third probe.
1592031000 Univ-R4 GB - r1.1 - 2012.07.23
0 = the compressor keeps on working if a low temperature alarm at the condenser is active;
1 = the compressor is switched off while the low temperature alarm is active. The regulation will restart after elapsing AC
delay time.
0 = the compressor keeps on working if a low temperature alarm at the condenser is active;
1 = the compressor is switched off while the low temperature alarm is active. The regulation will restart after elapsing AC
delay time.
0 = key functionality disabled;
1 = On Off function enabled;
2 = Energy Saving function enabled.
0 = disabled;
1 = enabled.