Plan View

Figure 2-2. System Dimensions

Weight Distribution and Service Clearance

Weight Distribution

The following table shows weights and dimensions used to calculate floor loading
for zSeries 800 systems. All floor loading calculations are intended for a raised floor
environment.
If you are planning an installation on a non-raised floor, contact a qualified
consultant or a structural engineer regarding your location choice to make sure the
floor is strong enough to support the weight of the machine.
The following figure and table show sample floor loading values for a zSeries 800
system.
2-4
zSeries 800: Installation Manual for Physical Planning
700 mm
(27.5 in)
30 mm
(1.2 in)
+
+
1000 mm
(39.4 in)
116 mm
(4.5 in)
Frame
Entry/Exit
Front
Rear
Table 2-4. zSeries 800 Maximum Frame Weight, Width, and Depth Used for Floor Loading
Calculations
Weight kg (lbs)
Width mm (in)
Depth mm (in)
Note: Weight includes covers. Width and depth are indicated without covers.
10 mm
(0.4 in)
+
+
1146 mm
(45.1 in)
720 mm
(28.3 in)
Dimension
(mm)
(in)
165 x 381
6.5 x 15.0
165 x 381
6.5 x 15.0
Level 04a, June 21, 2004
545 (1201)
700 (27.5)
1000 (39.4)