Guide Specifications - Bryant 926TA Product Data

Preferred two-stage 4-way multipoise, variable speed condensing gas furnace, series a
Table of Contents

Advertisement

General
System Description
Furnish a ______________________ 4- -way multipoise gas- -fired
condensing furnace for use with natural gas or propane (factory- -
authorized conversion kit required for propane); furnish external
media cabinet for use with accessory media filter or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas- -fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas- -fired central furnaces. Unit
will carry the CSA Blue StarR and Blue FlameR labels. Unit
efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer's Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer's recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed ball bearings, of _______hp,
and have infinitely variable speed from 600- -1200 RPM operating
only when motor inputs are provided. Blower motor shall be direct
drive and soft mounted to the blower housing to reduce vibration
transmission.
Filters
Furnace shall have reusable- -type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media
Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre- -painted steel.
Draft Inducer Motor
Draft inducer motor shall be two- -speed PSC design.

GUIDE SPECIFICATIONS

Primary Heat Exchangers
Primary heat exchangers shall be 3- -Pass corrosion- -resistant
aluminized steel of fold- -and- -crimp sectional design and applied
operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel
flow- -through of fin- -and- -tube design and applied operating under
negative pressure.
Controls
Controls shall include a micro- -processor- -based integrated
electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control, a
self- -test feature that checks all major functions of the furnace, and
a replaceable automotive- -type circuit protection fuse. Multiple
operational settings available, including separate blower speeds for
low heat, high heat, low cooling, high cooling and continuous fan.
Continuous fan speed may be adjusted from the thermostat.
Cooling airflow will be selectable between 325 to 400 CFM per
ton of air conditioning. Features will also include temporary
reduced
dehumidification when a T6- -PRH is selected as the thermostat.
Operating Characteristics
Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be________ AFUE.
Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure.
Dimensions
__________in. (mm); height___________in. (mm) (casing only).
Height shall be _________in. (mm) with A/C coil and
_________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single- -phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size
of HACR- -type designated circuit breaker shall be _________
amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
17
airflow
in
the
cooling
shall
be:
depth_________in.
mode
for
improved
(mm);
width

Advertisement

Table of Contents
loading

Table of Contents