Bryant 935CA Installation, Start-Up, Operating And Service And Maintenance Instructions

Single-stage, upflow/horizontal communicating, variable speed ecm, ultra low nox, 35-in tall condensing gas furnace

Advertisement

Quick Links

935CA
Single-Stage, Upflow/Horizontal Communicating,
Variable Speed ECM, Ultra Low NOx, 35-in Tall
Condensing Gas Furnace
Service and Maintenance Instructions
NOTE: Read the entire instruction manual before starting the
installation.
Approved for installations up to 5,400 feet (1646 meters)

TABLE OF CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 1 - Minimum Clearances to Combustible Materials for All Units
4
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 - Loose Parts Bag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CODES AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCE-
DURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . . . . . . 8
Table 3 - Minimum Free Area Required for Each Combustion Air
Opening or Duct to Outdoors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 4 - Minimum Space Volumes for 100% Combustion, Ventila-
tion and Dilution Air from Outdoors . . . . . . . . . . . . . . . . . . . . . . 10
CONDENSATE TRAP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Condensate Drain Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 5 - Condensate Trap Configurations . . . . . . . . . . . . . . . . . 12
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 6 - Evaporator Coil Spacer or Shield Requirements. . . . . 15
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 7 - Air Filter Selection and Duct Sizing - In. (mm) . . . . . 20
Table 8 - Opening Dimensions - In. (mm) . . . . . . . . . . . . . . . . . 20
Table 9 - Filter Media Pressure Drop (Clean) Versus Airflow - In.
W.C. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 10 - Filter Media Pressure Drop (Clean) Versus Face Velocity-
In. W.C. (Pa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 11 - Air Delivery - CFM (With Filter) . . . . . . . . . . . . . . . 21
GAS PIPING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 12 - Maximum Capacity of Pipe . . . . . . . . . . . . . . . . . . . . 24
ELECTRICAL CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 13 - Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
VENTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 14 - Vent Termination Kit for Direct Vent (2-pipe) Systems31
Table 15 - Hanger Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 16 - Approved Combustion-Air and Vent Pipe, Fitting and Ce-
ment Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 17 - Maximum Allowable Exposed Vent Length in Uncondi-
tioned Space - Ft. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 18 - Maximum Equivalent Vent Length - Ft. . . . . . . . . . . 41
Table 19 - Deductions from Maximum Equivalent Vent Length - Ft.
(M) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1E, with permission of National Fire Protection Association, Quincy, MA
02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI
Installation, Start-up, Operating and
on the referenced subject, which is represented only by the standard in its entirety.
Table 20 - Altitude Derate Multiplier for USA. . . . . . . . . . . . . . 49
Table 21 - Gas Valve Outlet Pressure for Gas Heat Values at Altitude
- 60,000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 22 - Gas Valve Outlet Pressure for Gas Heat Values at Altitude
- 80,000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 23 - Gas Valve Outlet Pressure for Gas Heat Values at Altitude
- 100,000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 24 - Gas Rate (CU ft./hr). . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 25 - Blower Off Delay Setup Switch . . . . . . . . . . . . . . . . 52
SERVICE AND MAINTENANCE PROCEDURES. . . . . . . . . . . . 53
WINTERIZATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
SERVICE GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
PARTS REPLACEMENT INFORMATION GUIDE . . . . . . . . . . . 68
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
TRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury and/or
death.
Carbon Monoxide (CO) is a colorless, odorless, and tasteless poisonous
gas that can be fatal when inhaled. Follow all installation, maintenance,
and service instructions. See additional information below regarding
the installation of a CO Alarm.
Most states in the USA and jurisdictions in Canada have laws that
require the use of Carbon Monoxide (CO) alarms with fuel burning
products. Examples of fuel burning products are furnaces, boilers, space
heaters, generators, water heaters, stoves/ranges, clothes dryers,
fireplaces, incinerators, automobiles, and other internal combustion
engines. Even if there are no laws in your jurisdiction requiring a CO
Alarm, it's highly recommended that whenever any fuel burning product
is used in or around the home or business that the dwelling be equipped
with a CO Alarm(s). The Consumer Product Safety Commission
recommends the use of CO Alarm(s). The CO Alarm(s) must be
installed, operated, and maintained according to the CO Alarm
manufacturer's instructions. For more information about Carbon
Monoxide, local laws, or to purchase a CO Alarm online, please visit the
following website. https://www.kidde.com.
A200352

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 935CA

  • Page 1: Table Of Contents

    935CA Single-Stage, Upflow/Horizontal Communicating, Variable Speed ECM, Ultra Low NOx, 35-in Tall Condensing Gas Furnace Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: Read the entire instruction manual before starting the START-UP, ADJUSTMENT, AND SAFETY CHECK ..47 installation.
  • Page 2: Required Notice For Massachusetts Installations2

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions REQUIRED NOTICE FOR MASSACHUSETTS INSTALLATIONS IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA-54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a.
  • Page 3: Safety Considerations

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: ALL DIMENSIONS IN INCH (MM) U.S. ECCN: Not Subject to Regulation (N.S.R.) SD5660-4 REV. - A210210 Fig. 1 – Dimensional Drawing SHIP WT. FURNACE SIZE LB (KG) CABINET WIDTH OUTLET WIDTH...
  • Page 4 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Combustion products must be discharged outdoors. Connect this CAUTION furnace to an approved vent system only, as specified in the “Venting” section of these instructions. FURNACE RELIABILITY HAZARD 5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks Failure to follow this caution may result in unit component damage.
  • Page 5: Introduction

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions load estimates and select the furnace. Excessive oversizing of the NOTICE furnace may cause the furnace and/or vent to fail prematurely, customer discomfort and/or vent freezing. Important Installation and Start-up Procedures...
  • Page 6: Codes And Standards

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions ELECTROSTATIC DISCHARGE (ESD) Table 2 – Loose Parts Bag PRECAUTIONS PROCEDURE DESCRIPTION Air Intake Pipe Flange Vent Pipe Flange CAUTION Pipe Flange Gaskets Sharp Tip Screws (Vent and Inlet Flanges) FURNACE RELIABILITY HAZARD...
  • Page 7 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions WARNING CARBON MONOXIDE POISONING / COMPONENT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death and unit component damage. Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space.
  • Page 8: Air For Combustion And Ventilation

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Location Relative to Cooling Equipment WARNING The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When CARBON MONOXIDE POISONING HAZARD installed parallel with the furnace, dampers or other flow control must Failure to follow this warning could result in personal injury or death.
  • Page 9 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 1. Adjoining rooms can be considered part of a space if: WARNING a. There are no closeable doors between rooms. b. Combining spaces on same floor level. Each opening shall have CARBON MONOXIDE POISONING HAZARD free area of at least 1 in.2/1,000 BTUh (2,000 mm2/kW) of the...
  • Page 10: Condensate Trap

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions EXAMPLES: Determining Free Area FURNACE WATER HEATER TOTAL INPUT 60,000 40,000 (100,000 divided by 3,000) 33.3 Sq. In. for each Single Duct or Opening 80,000 30,000 (110,000 divided by 2,000) 55.0 Sq. In. for each two Horizontal Ducts...
  • Page 11 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions CAUTION PROPERTY DAMAGE HAZARD Failure to follow this caution may result in burst water pipes and/or property damage. If a condensate pump is installed, a plugged condensate drain or a failed pump may cause the furnace to shut down.
  • Page 12: Installation

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 5 – Condensate Trap Configurations (Continued) Required Required Required A200091 Adapter Required Required Required A200092 Plate Required (accessory kit A200073 Required Required purchased A200093 separately) Offset Adapter Upflow installations utilizing the right side air return o...
  • Page 13 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Remove these for Horizontal Left Remove these for Horizontal Right Remove these for Upflow A200075 Fig. 13 – Drain Plugs WARNING A200065 Fig. 16 – Upflow - Offset of Condensate Drain...
  • Page 14 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 2. Install the grommet in the casing when required for direct-vent horizontal applications. 3. Allow for 6-3/8” (162 mm) of clearance underneath the furnace for the condensate trap and drain line. It is recommended to leave an additional 1”...
  • Page 15 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Alternate Horizontal Option - 8. Allow at least 1/4-in. per foot (20 mm per meter) of slope down and away from the furnace in horizontal sections of drain line. Remote Trap Installation Specific Steps 1.
  • Page 16 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions NOTE: The allowable use of the 8-in. spacer demonstration, see Table 6 A---COIL SHIELD Fig. 26. The spacer may taper to accommodate different coil/furnace width combinations but must always keep an 8-in. minimum height if 16-- 1/2 used.
  • Page 17 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions PERFORATED DISCHARGE DUCT FLANGE UPFLOW HORIZONTAL 90° 90° 120° 120° NOTE: For Upflow Right Side Return, use upflow offset installation for condensate trap. Refer to Table 11 footnotes for other return-air restrictions.
  • Page 18 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions NOTICE WARNING Upflow installations utilizing the right side air return FIRE, EXPLOSION, AND CARBON MONOXIDE opening should follow the Upflow Specific Steps - Offset POISONING HAZARD Installation to ensure the full opening is available for return Failure to follow this warning could result in personal injury, death, or ductwork.
  • Page 19 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions duct must be connected to ONLY the furnace supply-outlet-air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories.
  • Page 20: Air Ducts

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions return use in the horizontal position, see Fig. 29. If both side and bottom Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system openings are used, see Fig.
  • Page 21: Pa)

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 9 – Filter Media Pressure Drop (Clean) Versus Airflow - In. W.C. (Pa) Representative After-Market Filter Media* 16 x 25 Filter Factory-Accessory Factory-Accessory (406 x 635 mm) Washable Media* Fiberglass* Pleated* (1-in.
  • Page 22 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 11 – Air Delivery - CFM (With Filter) (Continued) COOLING AND HEATING AIR DELIVERY - CFM (Bottom Return With Filter) (SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2)
  • Page 23: Gas Piping

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions GAS PIPING WARNING WARNING FIRE OR EXPLOSION HAZARD A failure to follow this warning could result in personal injury, death, FIRE OR EXPLOSION HAZARD and/or property damage. Failure to follow this warning could result in personal injury, death, If local codes allow the use of a flexible gas appliance connector, and/or property damage.
  • Page 24: Electrical Connections

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions ELECTRICAL CONNECTIONS Table 12 – Maximum Capacity of Pipe NOMINAL LENGTH OF PIPE - FT (M) WARNING IRON PIPE SIZE 10 (3.0) 20 (6.0) 30 (9.1) 40 (12.1) 50 (15.2) IN. (MM)
  • Page 25 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions utility is sufficient to handle load imposed by this equipment. Refer to rating plate or equipment electrical specifications, see Table U.S.A. Installations: Make all electrical connections in accordance with the current edition of the National Electrical Code (NEC) NFPA 70 and any local codes or ordinances that might apply.
  • Page 26 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 3. Secure power cord to J-Box bracket with a strain relief bushing or a connector approved for the type of cord used. 4. Pull furnace power wires through 1/2-in. (12 mm) diameter hole in J-Box.
  • Page 27 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions ACCESSORIES communication plug is supplied with the User Interface. Refer to the instructions supplied with the User Interface for complete 1. Electronic Air Cleaner (EAC) details, see Fig. Connect an accessory Electronic Air Cleaner (if used) using 1/4-in.
  • Page 28 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions COMMUNICATION CONTINUOUS FAN OUTDOOR SW4 SETUP CONNECTOR (CF) AIRFLOW AIR TEMP SWITCHES SETUP SWITCHES CONNECTOR MODEL PLUG PL8 - PRESSURE CONNECTOR TRANSDUCER CONNECTOR SW1 SETUP SWITCHES AND BLOWER OFF- DELAY AIR CONDITIONING...
  • Page 29 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions THERMOSTAT THERMOSTAT A190367 See notes 1, 2, 4, 6, 7, 9, 10, 14 Fig. 43 – 1-Speed Variable Furnace with Single-Speed A190368 Fig. 45 – 1-Speed Variable Furnace with Single-Speed Heat Pump...
  • Page 30: Venting

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions VENTING WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
  • Page 31 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions RECOMMENDED SUPPORT FOR General NOTICE If this furnace replaces a furnace that was connected to a vent system or chimney, the vent or vent connectors of other remaining appliances may VENT TERMINATION need to be re-sized.
  • Page 32 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Locating the Vent Termination 1. Comply with all clearance requirements stated (see Fig. 60 Fig. 61) per application. General 2. The vent termination must be located at least 3 feet from an inside...
  • Page 33 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions with outside diameters of approximately 60 mm (2-3/8 inches). Any pipe diameter change should be made outside furnace casing in vertical pipe. Any change in diameter to the pipe must be made as close to the furnace as reasonably possible, see Fig.
  • Page 34 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions ADDITIONAL INFORMATION FOR NOTICE EXAMPLE FOR UPFLOW INSTALLATIONS. MAY BE APPLIED TO OTHER CONFIGURATIONS. POLYPROPYLENE VENTING SYSTEMS Polypropylene venting systems include flexible vent pipe. These flexi- ble vent pipes have a different equivalent vent length than straight sec- tions of PVC/ABS DWV vent pipe.
  • Page 35 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions MAY NOT be used for venting the furnace. Try the next larger diameter pipe NOTE: If the calculated Total Equivalent Vent Lengths results in Slope vent pipe back to the different diameter pipes for the vent and combustion air, select the larger furnace at least ¼”...
  • Page 36 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions can pass through the vent pipe adapter; it cannot pass through the inlet 4. Complete the vent and combustion air pipe installation by pipe adapter. connecting the concentric vent or by installing the required termination elbows, see Fig.
  • Page 37 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions WARNING ALIGN NOTCHES IN VENT PIPE COUPLING OVER STAND-OFF ON ADAPTER. TORQUE LOWER CLAMP 15 LB-IN. WHEN REMAINING VENT PIPE IS INSTALLED, TORQUE CARBON MONOXIDE POISONING HAZARD UPPER CLAMP TO 15 LB-IN.
  • Page 38 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Disassemble loose pipe fittings. Clean and cement using same NOTICE procedures as used for system piping. DO NOT CEMENT POLYPROPYLENE FITTINGS. RECOMMENDED SUPPORT FOR VENT (Direct Vent / 2-Pipe System ONLY)
  • Page 39 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions ALTERNATE COMBUSTION AIR CONNECTIONS HORIZONTAL RIGHT-VERTICAL VENT CONFIGURATION A11337 ALTERNATE HORIZONTAL LEFT-VERTICAL VENT CONFIGURATION COMBUSTION AIR CONNECTIONS A11327A Alternate combustion air connection. Rotate vent elbow to required position. Vent Pipe HORIZONTAL RIGHT-RIGHT VENT CONFIGURATION...
  • Page 40 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 16 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials MATERIALS 1. All pipe*, fittings*, primers**, and solvents** must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards 2.
  • Page 41 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 18 – Maximum Equivalent Vent Length - Ft. NOTE: Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Table 19 Deductions from Maximum Equivalent Vent Length to determine allowable vent length for each application.
  • Page 42 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Venting System Length Calculations The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent length of elbows used in the venting system, see Table Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
  • Page 43 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions No operable windows, doors or Clearance distances for intakes of any type within the items greater than 3 feet shaded areas of Wall A and B. (1 meter ) away from the...
  • Page 44 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions A12326 Fig. 60 – Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference. Refer to local codes which may supersede these standards and/or recommendations.
  • Page 45 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Avoid venting under a deck or large overhang. Recirculation could occur and cause performance or system problems. Ice build-up may occur. A12325 Fig. 61 – Ventilated Combustion Air and Non-Direct Vent Termination Clearance NOTE: The following is based upon National codes for gas appliances and is provided as a reference.
  • Page 46 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions ¾ in. (222mm) for 3 in. (76mm) ¾ in. (172mm) for 2 in. (51mm) 12 in. (305mm) min. separation between bottom of combustion air and bottom of vent (Typ.) A13305 Fig. 62 – Combustion Air and Vent Pipe Termination for Direct Vent (2-Pipe) System...
  • Page 47: Start-Up, Adjustment, And Safety Check

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Ventilated Combustion Air intake pipe Pipe hangar 3” (76 mm) 12” (305 mm) Ventilated Combustion Air intake termination in crawl space CRAWL SPACE highest level of insulation ATTIC A10497 Fig. 64 – Vent Terminations for Ventilated Combustion Air START-UP, ADJUSTMENT, AND SAFETY EAC-1 terminal is energized whenever blower operates.
  • Page 48 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Prime Condensate Trap with Water 3. Configure the setup switches as necessary for the application. 4. Replace blower door. CAUTION NOTE: If a bypass humidifier is used, setup switch SW1-4 (Comfort/Efficiency) should be in OFF=Efficiency position. This...
  • Page 49 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions m.Remove manometer from the inlet pressure tap of the gas valve. n. Tighten set screw on inlet tower pressure tap with 3/32−in. hex wrench, or if 1/8−in. NPT plug was removed, apply pipe dope...
  • Page 50 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 21 – Gas Valve Outlet Pressure for Gas Heat Values at Table 22 – Gas Valve Outlet Pressure for Gas Heat Values at Altitude - 60,000 Altitude - 80,000 (Tabulated Data Based on 60,000 BTUH Input for 0-ft (0m) to...
  • Page 51 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Table 23 – Gas Valve Outlet Pressure for Gas Heat Values at c. Measure time (in seconds) for gas meter to complete 1 revolution Altitude - 100,000 and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.
  • Page 52 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions e. Check for gas leaks and verify furnace operation. Table 25 – Blower Off Delay Setup Switch 7. Set temperature rise. The furnace must operate within the SETUP SWITCH temperature rise ranges specified on the furnace rating plate.
  • Page 53: Service And Maintenance Procedures

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 7. Review Owner’s Manual with owner. CAUTION 8. Attach literature packet to furnace. 9. Attach entire literature packet to furnace. FURNACE OVERHEATING HAZARD SERVICE AND MAINTENANCE PROCEDURES Failure to follow this caution may result in reduced furnace life.
  • Page 54 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions CAUTION ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental pollution. Remove and recycle all components or materials (i.e. oil, refrigerant, control board, etc.) before unit final disposal. Electrical Controls and Wiring...
  • Page 55 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions Care and Maintenance 5. Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner. Perform any service or maintenance to the WARNING accessories as recommended in the accessory instructions.
  • Page 56 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Remove two screws holding blower assembly to blower deck and WARNING slide blower assembly out of furnace. NOTE: On 66100C21 size, the top screw securing blower to shelf must ELECTRICAL SHOCK HAZARD be removed in order to remove the blower, see Fig.
  • Page 57 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions IGNITOR FLAME POSITION SENSOR A190266 Fig. 73 – Igniter Position - Back View 1. Disconnect power at external disconnect, fuse or circuit breaker. 2. Turn off gas at external shut-off or gas meter.
  • Page 58 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions The igniter does NOT require annual inspection. Check igniter 11. Remove the relief tube from the port on the collector box and the resistance before removal, see Fig. trap. 1. Turn off gas and electrical supplies to furnace.
  • Page 59: Winterization

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 12. Check for gas leaks. WARNING WARNING ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death, or property damage.
  • Page 60 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 4. Remove the top unused rubber plug from the port on the collector flame is sensed or until the 2-second flame proving period box opposite the condensate trap. begins. d. Flame Proving: When the burner flame is proved at the flame 5.
  • Page 61 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions high-cooling. If starting up in low-cooling, the furnace control CPU the furnace control reverts back to non-dehumidification mode. determines the low-cooling on-time (from 0 to 20 minutes) which is The cooling operation described in item 3. above also applies to permitted before switching to high-cooling.
  • Page 62 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions BLWM will operate at high cooling airflow. When the thermostat is the blower motor BLWM at cooling airflow or the mid-range satisfied, the blower motor BLWM will operate an additional 90 sec airflow, whichever is lowest.
  • Page 63 START Is AMBER LED status light on? Is there 115V at L1 and L2? Is door switch closed? Close the door switch. Is there 24V at SEC-1 and SEC-2? Is there 115V going to switch? Is circuit breaker closed? Check for continuity in wire from circuit Replace furnace control.
  • Page 64 11 NO PREVIOUS CODE – Status codes are 32 LOW-HEAT PRESSURE SWITCH DID 43 LOW-HEAT PRESSURE SWITCH OPEN 45 CONTROL CIRCUITRY erased after 72 hours or can be manually NOT CLOSE OR REOPENED – If open WHILE HIGH-HEAT PRESSURE LOCKOUT Auto-reset erased by putting setup switch SW1-1 in longer than 5 minutes, inducer shuts off SWITCH IS CLOSED - Check for:...
  • Page 65 25 INVALID MODEL SELECTION OR 41 BLOWER MOTOR FAULT – Indicates the Turn power back on. Is there 115VAC at You have an open wire or bad SETUP ERROR – If status code 25 only blower failed to reach 250 RPM or the PL14-5 and PL14-4? terminal on either the BLACK or flashes 4 times on power-up the control is...
  • Page 66 935CA: Installation, Start-up, Operating and Service and Maintenance Instructions 346011-2 rev A A200312 Fig. 76 – Wiring Diagram Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
  • Page 67: Service Guide

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions SERVICE GUIDE LED CODES STATUS CONTINUOUS OFF Check for 115VAC at L1 and N, and 24VAC at SEC-1 and SEC-2 CONTINUOUS ON Control has 24VAC power. RAPID FLASHING Line voltage (115VAC) polarity reversed. Check for poor or no ground (GND).
  • Page 68: Parts Replacement Information Guide

    935CA: Installation, Start-up, Operating and Service and Maintenance Instructions PARTS REPLACEMENT INFORMATION Media Cabinet (when used) GUIDE Gas Control Group Burner Casing Group Flame sensor Blower door Gas valve Bottom plate Hot surface igniter Control door Manifold Door knob assembly...

Table of Contents