Clearance Requirements; Mantel And Trim Clearances - Jøtul GF 200 DV Installation And Operation Instructions Manual

Jotul lillehammer gas heater installation and operation instructions gf 200 dv
Table of Contents

Advertisement

Clearance to Combustibles
Minimum Stove Clearance
Rear
0"
Ceiling
17"
Corner
2"
Right Side
2"
Left Side
*10"
* Necessary for complete access to pull out required Lighting
Instructions Plate.
Minimum Vent Pipe Clearance
Horizontal runs:
Off the top of the pipe -
Off the sides and bottom -
Vertical runs:
All sides
-
See Figures 4 and 5.

Mantel and Trim Clearances

24"or greater depth
or ceiling
17"
432 mm
10"
255 mm
Figure 3. Mantel / Trim Clearances
(0mm)
(432mm)
(51mm)
(51mm)
(255mm)
2" (26mm)
1" (26mm)
1" (26mm)
12" or less
6" or
less
2"
6"
51 mm
153 mm
1" deep
trim
must be
2" off
the top of
the
stove.
Parallel Installation
Rear Wall Clearance: 0" (ZERO mm)
Max.
Alcove
Depth
24"
610
mm
Left Side*
10"
230 mm
* Allow 10" on left side of the appliance
for complete access to the lighting
instructions and control valve.
Figure 4. Clearances with stove parallel to the walls
Alcove Installation
Maximum Depth:
Minimum Width:
Minimum Ceiling Height:
Corner Installation
2"
51mm
Figure 5. Clearance to rear corners.
2"
Right
25
Side
mm
24" (610mm)
35" (890mm)
42" (1067mm)
2"
51mm
7