Remote Command Inputs

The function of Acknowledge, Signal Silence, and System Reset can be executed from remote switches. The
switches are wired to IZ-8F circuits which must be programmed for this special operation. Additional functions
are outlined below.
Presignal Inhibit: Zone 1. Program zone as non-alarm and supervisory. This command is used to inhibit
presignal operation. Upon entering presignal, the CPU checks zone 1 on all IZ-8F modules. If the zone is active
(shorted), all presignal or PAS operation will be ignored.
Emergency Alert: Zone 5. Program zone as Non-Alarm and supervisory. Use as an evacuation signal for
tornados, bomb-scares and other non-fire emergency situations. If the control panel is not in alarm, activation
(short) on zone 5 will activate all Notification Appliance Circuits and output relays that are mapped to zone 5, with
a steady signal. Programmed March Time or Temporal code is ignored. A fire alarm takes priority over an
emergency alert. Notification Appliance Circuits used for fire must be programmed for MTC or Code 3 operation.
Emergency Alert is for local signalling only. Do not map to "Remote Signalling/Municipal Tie" outputs.
Acknowledge: Zone 6. Program circuit as Non-Alarm and supervisory. Use to remotely execute an Acknowledge
command without the need of an ACM-16ATF annunciator.
Signal Silence: Zone 7. Program circuit as Non-Alarm and supervisory. Use to remotely execute the Signal
Silence command without the need of an ACM-16ATF annunciator.
System Reset: Zone 8. Program circuit as Non-Alarm and supervisory. Use to execute the System Reset function
without the need of an ACM-16ATF annunciator.
Emergency
Alert
Acknowledge
Signal
Silence
Presignal
Inhibit
Reset
IZ-8F
Figure 6-8: Remote Command Input Connections
1) Initiating circuits used as command circuits are supervised, power limited, and may be connected to limited-energy cable.
2) Maximum line resistance allowed due to wiring is 100 ohms.
S200 15032 Rev C 02/22/96 P/N 15032:C
44