Connect Electricity 
WARNING
Do not use an extension cord or an adapter plug with 
this appliance. 
The water heater must be electrically grounded in 
accordance with local codes and ordinances or, in the 
absence of local codes, in accordance with the 
Na onal Electrical Code, ANSI/NFPA No. 70. 
Indoor water heaters are equipped with a three‐
prong (grounding) plug for your protec on against 
shock hazard and should be plugged directly into a 
properly grounded three‐prong receptacle.  Do not 
cut or remove the grounding terminal from this plug. 
Do not rely on the gas or water piping to ground the 
water heater.  A screw is provided in the junc on box 
for the grounding connec on. 
The water heater requires 120 VAC, 60 Hz power from 
a properly grounded circuit. 
If using the 5 foot long power cord, plug it into a 
standard 3 prong 120 VAC, 60 Hz properly grounded 
wall outlet.   
On outdoor models, a disconnect switch must be 
provided and installed for the incoming 120 VAC 
power.  It should be a type that is suitable for outdoor 
use.  Check the Na onal Electrical Code, ANSI/NFPA 
70 and your local codes for a proper switch type to 
use in your area. 
The wiring diagram is located on the Technical Sheet 
a ached to the inside of the front cover. 
20 
Adjust for High Al tude  
For the V75i/e, on the SW1 DIP switch (tan switches), 
set switches 2 and 3 to the values shown in table 
below for your al tude.  The default se ng for the 
appliance is 0‐2000   (0‐610 m) with switches No. 2 
and No. 3 in the OFF posi on.  When the DIP switch is 
adjusted, it is not necessary to adjust the gas pressure 
se ng for high al tude. 
0‐2000   (0‐610 m) 
2001‐5200   (610‐1585 m) 
5201‐7700   (1585‐2347 m) 
7701‐10200   (2347‐3109 m) 
The V65i/e is not approved for high al tude 
opera on. 
Adjust for Vent Length  
(indoor models only) 
Adjust switch No. 1 in the SW1 DIP switch (tan 
switches) if required.  Refer to the sec on "Maximum 
vent length".
Checklist for Gas and Electricity 
□ 
A manual gas control valve is placed in the gas 
line to the water heater. 
□ 
Check the gas lines and connec ons for leaks. 
□ 
Confirm that the gas inlet pressure is within 
limits. 
□ 
Confirm that the water heater is rated for the gas 
type supplied. 
□ 
Confirm that the electricity is supplied from 120 
VAC, 60 Hz power source and is in a properly 
grounded circuit. 
□ 
An extension cord or an adapter plug has not 
been used with the water heater. 
□ 
For indoor models verify that switch No. 1 in the 
SW1 DIP switch (tan switches) has been adjusted 
for vent length if necessary.  Refer to the sec on 
on Maximum Vent Length. 
Value Series Manual 
Al tude 
Switch No. 
 
SW1 
SW1 
Switch No. 
OFF 
OFF 
OFF 
ON 
ON 
OFF 
ON 
ON 