ERTICAL VENT THROUGH THE ROOF
It is the sole responsibility of the installer to
adhere to all current local codes and/or ANSI
Z223.1 / CSA.B149.1 latest editions for all
venting requirements, and practices.

Use an approved 'B-vent' termination cap
as supplied by the manufacturer of the ap-
proved 'B-vent'.

When vent and combustion air are taken
through the roof, the exhaust vent should
always terminate higher than the combus-
tion air intake, to prevent recycling the
products of combustion back into the
heater

At most a quantity of three 90° elbows can be installed in a vertical vent
11A. Combined System Length: Tube Heater + Vent + Combustion Air Duct
MINIMUM VENT LENGTH: (Vented or Unvented)

Minimum vent length of 3 ft (91 cm) is required (NOTE: 200,000 LP: Minimum 8 ft (244 cm)
MAXIMUM SYSTEM LENGTH (includes: Tube Heater length + combustion air duct + vent):

Each 90° elbow in the system has an equivalent length of 5 ft.

A maximum of 2 elbows are allowed in any portion (duct, tube heater, vent) with the ex-
ception of up to three 90° elbows in a vertical vent run through the roof

The maximum length of combustion air duct to any heater is not to exceed 30 feet

Exceeding the allowable lengths in the table below can create combustion and/or conden-
sation problems and will void CSA Design Certification and the heater warranty.
Max. Combined
Input
System Length*
(Btuh)
Do Not Exceed
45,000
60,000
80,000
110,000
100 ft
130,000
100 ft
150,000
100 ft
175,000
120 ft
200,000
120 ft
* Do not exceed the Maximum Combined System Length regardless of the allowed maximum
length of individual vent or combustion air duct
:
Max. Vent
Length*
60 ft
Up to 30 ft
60 ft
Up to 30 ft
80 ft
Up to 40 ft
Up to 40 ft
Up to 40 ft
Up to 40 ft
Up to 50 ft
Up to 50 ft
FIGURE 22
Approved
Cap
24"
60 cm
A p p r o v e d
'B' Vent
Max. Air Duct
Length*
Example
Up to 20 ft
150,000 Btuh Heater:
Up to 30 ft
Tube Heater Length 50 ft
Up to 30 ft
1 x 90° elbow (vent) 5 ft
Up to 30 ft
Straight vent
Up to 30 ft
1 x 90° elbow (duct) 5 ft
Up to 30 ft
Air Duct
Up to 30 ft
Combined Length
Up to 30 ft
Max. Allowed
31
9
Up
to
12
If roof slope exceeds 9:12
consult NFPA-54 ANSI
Z223.1 or CSA-B149.1
20 ft
17 ft
97 ft
100 ft
STW-JZ / IW I&O Manual
RD: AUG 2013
:
IM101229
RL: 12B- BA