L1
SUPPLY VOLTAGE
208-230/3/60
NOTE 3
C
T1
T2
T1
T3
IIC
C
H
L1
3
1
F
FS
4
5
3
IIC
6
8
9
7
10
12
11
R
G
W
Y1
Y/Y2
INSTALLER/SERVICEMAN
EQUIP. STATUS
STATUS LIGHT
ON
NORMAL OPERATION
OFF
NO POWER OR
INTERNAL CONTROL
FAULT
IGNITION FAILURE
1 BLINK
OPEN ROLLOUT
SWITCH
OPEN AUX. LIMIT
SWITCH
2 BLINKS
PRESSURE SWITCH
OPEN
3 BLINKS
WITHOUT INDUCER ON
4 BLINKS
OPEN LIMIT SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
OUTPUT DELAY
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
GPG13(36)3** WIRING DIAGRAM
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
CH
C
T3
T2
C
C
F
FC
CM
NOTE 4
(MED)
E
M
V
M
2
1
NOTE 2
T
R
IG
N
FS
LS
AL
S
RS
G
V
PS
HPS
C
NOTE 5
PLF
C
CHECK
-
GAS FLOW
OR
GAS PRESSURE
GAS VALVE
FLAME SENSOR
FLAME ROLLOUT
OR
BAD SWITCH
AUX. LIMIT OPEN
CHECK
PRESSURE SWITCH
CHECK
PRESSURE SWITCH
MAIN LIMIT OPEN
BAD SWITCH
3 MIN. COMP.
L2
L3
COMPONENT LEGEND
ALS
AUXILIARY LIMIT SWITCH
COMP
COMPRESSOR
CONDENSER MOTOR
CM
C
CONTACTOR
CH
CRANKCASE HEATER
EVAPORATOR MOTOR
EM
F
FUSE
FC
FAN CAPACITOR
FS
FLAME SENSOR
GND
EQUIPMENT GROUND
GV
GAS VALVE
INTEGRATED IGNITION CONTROL
IIC
IGN
IGNITOR
LS
LIMIT SWITCH
PLF
FEMALE PLUG/CONNECTOR
PS
PRESSURE SWITCH
2
RS
ROLLOUT SWITCH
TR
TRANSFORMER
VM
VENT MOTOR
HPS
HIGH PRESSURE SWITCH
NOTES
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF
INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING
SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT
TERMINAL (IIC)
3 SPEED MOTOR
BK - HIGH SPEED
BL - MEDIUM SPEED
RD - LOW SPEED
6
5
4
5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT
3 2
1
TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.
6. USE COOPER CONDUCTORS ONLY.
USE NEC CLASS 2 WIRE.
NO
ECONOMIZER
WH
GR
RD
YL
BL
36
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
WIRE CODE
BK BLACK
BL BLUE
BR BROWN
GR GREEN
OR ORANGE
PK PINK
PU PURPLE
RD RED
WH WHITE
YL YELLOW
BL/PK BLUE/PINK
THERMOSTAT FIELD WIRING
2 STAGE COOLING WITH ECONOMIZER
OPTION
W
G
R
Y
C
HIGH VOLTAGE
LOW VOLTAGE
208-230/3/60
W
WH
G
GR
R
RD
Y1
PU
Y2
C
BL
0140G01001 REV. A