Goodman APG152407041A Series Technical Manual

Package gas units.
Hide thumbs

Advertisement

TECHNICAL MANU
TECHNICAL MANU
TECHNICAL MANU AL
TECHNICAL MANU
TECHNICAL MANU
Refer to Service Manual RS6300007 for installation, operation, and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
Select Models qualify for the 2009 and 2010 Federal Tax Credits for Energy Efficiency**
®
US
C
**Note that these tax credits are subject to specific requirements set forth in the American Recovery and
Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult
a tax professional if they have questions about the applicability of these credits.
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury due to
improper service procedures or services performed by an unqualified person.
*PG15
Package Gas Units
Copyright © 2007 - 2009-2010 Goodman Manufacturing
AL
AL
AL
AL
Company, L.P.
RT6313001r11
April 2010

Advertisement

   Related Manuals for Goodman APG152407041A Series

   Summary of Contents for Goodman APG152407041A Series

  • Page 1

    **Note that these tax credits are subject to specific requirements set forth in the American Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consumers consult a tax professional if they have questions about the applicability of these credits.

  • Page 2: Product Identification

    Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Goodman will not be responsible Installation and repair of this unit WARNING WARNING...

  • Page 3

    **Note that these tax credits are subject to specific requirements set forth in the American Recovery and Reinvestment Act of 2009 and in the Internal Revenue Code. Goodman recommends that consum- ers consult a tax professional if they have questions about the applicability of these credits.

  • Page 4: Product Design

    PRODUCT DESIGN *PG15 Package Gas Units are designed for outdoor installa- - These Scroll compressors use "POE" orpolyolester oil which tions only in either residential or light commercial applica- is NOT compatible with mineral oilbased lubricants like 3GS. tions and are available in 2, 2-1/2, 3, 3-1/2, 4 & 5 ton sizes. "POE"...

  • Page 5: Outside Slab Installation, Rooftop Installation

    PRODUCT DESIGN Location and Clearances NOTE: To ensure proper condensate drainage, unit must be installed in a level position. NOTE: To ensure proper condensate drainage, unit must be In installations where the unit is installed above ground level installed in a level position. and not serviceable from the ground (Example: Roof Top in- stallations) the installer must provide service platform for ser- vice person with rails or guards in accordance with local codes...

  • Page 6

    PRODUCT DESIGN High Altitude Derate - U.S. Installations Only tude increases, there is a natural reduction in the density of both the gas fuel and combustion air. This kit will provide the MPORTANT NOTE: The gas/electric units naturally derate proper design certified input rate within the specified altitude with altitude.

  • Page 7: Unit Dimensions

    PACKAGE GAS SPECIFICATIONS UNIT DIMENSIONS FLUE EXHAUST HOOD 18 7/16 FLUE EXHAUST 1 3/8 5 1/2 7 15/16 SUCTION/LIQUID PRESSURE PORTS 2 3/4 BEHIND COMPRESSOR ACCESS PANEL COMBUSTION AIR INTAKE RETURN HEAT EXCHANGE ACCESS PANEL 4 3/4 GAS SUPPLY ENTRANCE SUPPLY CONDENSATE DRAIN CONNECTION 3/4"...

  • Page 8

    PACKAGE GAS SPECIFICATIONS *PG15[24-37]***41AA *PG152407041AA *PG153009041AA *PG153609041AA *PG153709041AA COOLING COOLING CAPACITY, BTUH CAPACITY HIGH STAGE 23,200 29,000 35,400 35,000 LOW STAGE 24,400 SEER / EER 15.0 / 12.0 14.5 / 12.0 15.0 / 11.0 14.5 / 12.0 HEATING BTUH INPUT (US) HIGH FIRE 69,000 92,000 92,000...

  • Page 9

    PACKAGE GAS SPECIFICATIONS *PG15[42-60]***41AA *PG154211541AA *PG154811541AA *PG154911541AA *PG156014041AA COOLING CAPACITY, BTUH HIGH STAGE 40,000 47,500 47,000 56,500 LOW STAGE 35,000 33,000 41,000 SEER/EER 14.5 / 12.0 15.0 / 11.0 15.0 / 12.0 14.0 / 10.1 BTUH INPUT (US) HIGH FIRE 115,000 115,000 115,000...

  • Page 10

    PACKAGE GAS SPECIFICATIONS *PG15[36-60]***41AB *PG153609041AB * PG154811541AB *PG156014041AB COOLING COOLING CAPACITY, BT UH CAPACITY HIGH STAGE 35,400 47,500 56,500 LOW STAGE 24,400 35,000 41,000 SEER/EER 15.0 / 11.0 15.0 / 11.0 14.0 / 10.1 HEATING BTUH INPUT (US) HIGH FIRE 92,000 115,000 138,000...

  • Page 11

    Square to Round Adapter w/ 16" Round Horizontal Application, Small and Medium Chassis SQRPGH103 Square to Round Adapter w/ 18" Round Horizontal Application, Large Chassis PGFR101/102/103 Internal Filter Rack All Chassis External Horizontal Filter Rack for Goodman/Amana Gas/Electric GPGHFR101-103 & Multi-position Package Units All Chassis CDK36 Flush Mount Concentric Duct Kit...

  • Page 12: Blower Performance Data

    BLOWER PERFORMANCE DATA *PG15[24-36]***41A* *PG15240701A* - Rise Range: 35° - 65° T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 - Cooling Speed T4 - Cooling Spped T5 - Cooling Spped Unit Static WATTS AMPS RISE WATTS AMPS RISE...

  • Page 13

    BLOWER PERFORMANCE DATA *PG15[42-60]***41A* *PG154211541A* - Rise Range: 45° -75° T1 - 1st Stage Heating Speed T2 - 2nd Stage Heating Speed T3 Cooling Spped T4 Cooling Speed T5 - Cooling Speed Unit Static WATTS AMPS RISE WATTS AMPS RISE WATTS AMPS WATTS...

  • Page 14

    BLOWER PERFORMANCE DATA...

  • Page 15

    COOLING PERFORMANCE DATA *PG1524***41A*...

  • Page 16

    COOLING PERFORMANCE DATA *PG1524***41A*...

  • Page 17

    COOLING PERFORMANCE DATA *PG1530***41A*...

  • Page 18

    COOLING PERFORMANCE DATA *PG1530***41A*...

  • Page 19

    COOLING PERFORMANCE DATA *PG1536***41A* TAGE...

  • Page 20

    COOLING PERFORMANCE DATA *PG1536***41A* TAGE...

  • Page 21

    COOLING PERFORMANCE DATA *PG1536***41A* TAGE...

  • Page 22

    COOLING PERFORMANCE DATA *PG1536***41A* TAGE...

  • Page 23

    COOLING PERFORMANCE DATA *PG1537***41A*...

  • Page 24

    COOLING PERFORMANCE DATA *PG1537***41A*...

  • Page 25

    COOLING PERFORMANCE DATA *PG1542***41A*...

  • Page 26

    COOLING PERFORMANCE DATA *PG1542***41A*...

  • Page 27

    COOLING PERFORMANCE DATA *PG1548***41A* TAGE...

  • Page 28

    COOLING PERFORMANCE DATA *PG1548***41A* TAGE...

  • Page 29

    COOLING PERFORMANCE DATA *PG1548***41A* TAGE...

  • Page 30

    COOLING PERFORMANCE DATA *PG1548***41A* TAGE...

  • Page 31

    COOLING PERFORMANCE DATA *PG1549***41A* TAGE...

  • Page 32

    COOLING PERFORMANCE DATA *PG1549***41A* TAGE...

  • Page 33

    COOLING PERFORMANCE DATA *PG1549***41A* TAGE...

  • Page 34

    COOLING PERFORMANCE DATA *PG1549***41A* TAGE...

  • Page 35

    COOLING PERFORMANCE DATA *PG1560***41A* TAGE...

  • Page 36

    COOLING PERFORMANCE DATA *PG1560***41A* TAGE...

  • Page 37

    COOLING PERFORMANCE DATA *PG1560***41A* TAGE...

  • Page 38

    COOLING PERFORMANCE DATA *PG1560***41A* TAGE...

  • Page 39: Cooling Performance Data

    COOLING PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.

  • Page 40: Wiring Diagrams

    WIRING DIAGRAMS [A/G]PG15[24-60]***41** HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. YL/BK YL/BK BL/PK SEE NOTE 6 BL/PK COMP POWER SUPPLY 208-230/1/60...

  • Page 41

    WIRING DIAGRAMS [A/G]PG15[24-60]***41** HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS WARNING UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SUPPLY VOLTAG E 208-230/1/60 COMPONENT LEGEND FACTORY WIRING FACTORY WIRING AUXILLARY LIMIT SWITCH LINE VOLTAGE...