No.
Item
15
Central control
1) Setting at the central controller side enables to select
mode selection
2) Setup contents
16
Energy-saving
1) Selecting [AUTO] mode enables an energy-saving to
control
2) The setup temperature is shifted (corrected) in the
3) Data (Input value room temp. Ta, Outside temp. To, Air
4) The setup temperature is shifted every 20 minutes,
17
Max. frequency
1) This control is operated by selecting [AUTO] operation mode.
cut control
2) COOL operation mode:
Outline of specifications
the contents which can be operated on the wired
remote controller.
• In case of TCC-LINK Central remote controller
(TCB-SC642TLE2)
[Individual]:
Operated by wired remote controller
([After-push precedence])
[Central 1]:
START / STOP operation by wired remote controller
is unavailable.
[Central 2]:
START / STOP , MODE change and TEMP. setting by
wired remote controller are unavailable.
[Central 3]:
MODE change and TEMP . setting by wired remote
controller are unavailable.
[Central 4]:
MODE change by wired remote controller is
unavailable.
• In case of the wireless remote controller, the con-
tents to be operated are same though the display
lamp does not change.
If an item prohibited by the central control mode is
operated from the remote controller, it is notified with
receiving sound Pi, Pi, Pi, Pi, Pi (5 times)
be operated.
range not to lose the comfort ability according to input
values of various sensors.
volume, Indoor heat exchanger sensor temp. Tc) for
20 minutes are taken the average to calculate correc-
tion value of the setup temperature.
and the shifted range is as follows.
In cooling time: +1.5 to – 1.0K
In heating time: –1.5 to +1.0K.
It is controlled according to the following
figure if To < 28°C.
Ta ˚C
Normal control
+4
+3
Tsc
Max. frequency is
restricted to approximately
the rated cooling frequency
3) HEAT operation mode:
It is controlled according to the following
figure if To > 15°C.
Ta ˚C
Tsh
–3
–4
Normal control
– 37 –
Remarks
Display at wired remote
controller side (No display)
[
] goes on.
[
] goes on.
[
] goes on.
[
] goes on.
Max. frequency is
restricted to approximately
the rated heating frequency