Flue Installation - Worcester Greenstar Ri User Manual

Wall hung rsf gas fired condensing boiler
Table of Contents

Advertisement

Edge of
case
195mm
Turret
Clamp
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER BOSCH GREENSTAR Ri
8 716 109 699a (05/05)
93mm
(250mm min)
Flue

FLUE INSTALLATION

WALL
HORIZONTAL FLUE
(60/100mm diameter)
For vertical flues and 80/125mm horizontal flues,
please refer to separate instructions supplie with
127mm
the flue kits.
NOTE: to ease the assembly of flue components,
apply silicone lubricant to sealing surfaces.
The instructions for the 60/100mm diameter flue
are shown below.
MEASURING THE FLUE (Standard Flue):
Measure from the outside wall to the centre
line of the flue turret.
Subtract 93mm from the length L to give
the correct dimension to the flue elbow
connection.
The terminal section should be cut to this
dimension, however it must not be shorter
than 250mm.
After cutting the end must be square and
free from burrs to prevent damage to the
flue seals.
20
FLUE INSTALLATION