AU482FIBHA Fault Code List

Digital
Location
readout
TE circuit of defrost
01
temperature
outdoor unit
TA circuit of ambient
02
temperature sensor
TS circuit of suction
03
line
sensor
TD circuit of discharge
line
04
sensor
TC circuit of central
temperature sensor,
05
outdoor unit
condenser
Overcurrent
06
Current
circuit
07
Overload
08
circuit
compressor
IPM protection
09
Base board EEPROM
10
error
Discharge
temperature protection
11
(TD)
The detected sensor value is below 20H
sensor,
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. The fault is fixable.
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. The fault is fixable.
The detected sensor value is below 20H
temperature
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. The fault is fixable.
After 3 minutes of compressor operation, the
temperature
detected
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. Fixable when below 80°C.
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit)
for 60 seconds. 。
An alarm is given five seconds after the
current limit is exceeded. Where there are 3
alarms within 30 minutes, the fault code is
displayed. The fault is not fixable.
transformer
When the compressor is shut off, the detected
current of current sensor is above 15A, and
when the compressor is started, the operating
frequency is above 60Hz and the detected
current is below 5A. The fault is fixable.
protector
The overload protector of inverter compressor
of
inverter
is activated.
IPM
overtemperature and undervoltage. When the
fault occurs three times within 30 minutes, an
alarm is given and the fault is not fixable.
857 EEPROM data access error, 11 flashes.
The fault is not fixable.
line
When
temperature detected by TD1 sensor is above
120°C. The compressor is shut off in 5
seconds and an alarm is given. Where there
>a__WcU[S^ <[c >a`V[e[a`Wc
Description
sensor
value
is
overcurrent,
the
compressor
is
-169-
Is it
fixable
Yes
Yes
Yes
below
20H
Yes
Yes
No
short-circuit,
started,
the