11. Failure code and troubleshooting

AU242FHBHA Fault Code List

Number of
flashes by
fault
indicator
TE circuit of defrost
1
temperature
outdoor unit
TA circuit of ambient
2
temperature sensor
TS circuit of suction
3
line
sensor
TD
discharge
4
temperature sensor
TC circuit of central
temperature sensor,
5
outdoor unit
condenser
Overcurrent
6
IPM protection
9
Base board EEPROM
10
error
Discharge
temperature
protection (TD)
11
857-to-809
12
transmission error
High pressure switch
13
circuit
Location
The detected sensor value is below 20H
sensor,
(open-circuit) or above 1000H (short-circuit) for
60 seconds. The fault is fixable.
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds. The fault is fixable.
The detected sensor value is below 20H
temperature
(open-circuit) or above 1000H (short-circuit) for
60 seconds. The fault is fixable.
circuit
of
After 3 minutes of compressor operation, the
line
detected
(open-circuit) or above 1000H (short-circuit) for
60 seconds. Fixable when below 80°C.
The detected sensor value is below 20H
(open-circuit) or above 1000H (short-circuit) for
60 seconds. 。
An alarm is given five seconds after the current
limit is exceeded. Where there are 3 alarms
within 30 minutes, the fault code is displayed.
The fault is not fixable.
IPM overcurrent, short-circuit, overtemperature
and undervoltage. When the fault occurs three
times within 30 minutes, an alarm is given and
the fault is not fixable.
857 EEPROM data access error, 11 flashes.
The fault is not fixable.
line
After
temperature detected by TD1 sensor is above
120°C. The compressor is shut off in 5 seconds
and an alarm is given. Where there are 3
alarms within 30 minutes, the fault code 11 is
displayed. The fault is not fixable.
The high pressure switch is activated. The fault
is corrected after the normal pressure is
restored for 2 minutes.
>a__WcU[S^ <[c >a`V[e[a`Wc
Description
sensor
value
is
the
compressor
is
-163-
Is it
fixable
Yes
Yes
Yes
below
20H
Yes
Yes
No
started,