electronic
expansion valve
gas pipe temp. sensor
CN5
liquid pipe temp. sensor
CN11
ambient temp.
float switch
sensor
indoor temp
CN
1 2
sensor
CN2
LED3 LED2
LED1
SW1
CN13
CN1
receive display PCB
choice of remote
controller type
CN14
choice of wired
controller type
A
B
C
D
wired controller
outdoor
communication
B:Black
BL:Blue
BR:Brown
R:Red
W:White
Y/G:Yellow/Green
AE07/09/12/14/18/242FCBKA
Indoor unit wiring diagram
M
for built-in EEV type
1
2
3
4
5
6
CN6
temperate
water
CN9
sensor
2
1
serial
unit code setting
24
CN16
Indoor control board
CN15
2
1
RL4
RL3
RL7 RL6
RL5
CN1
CN10
CN4
CN7
1
7 6
5
1
1
2
4
3
2
3
2
R
R
fan
capacitor
connector
M
earthing
pump motor
Y/G
indoor fan motor
negative ion generator or
high voltage accumulator
electronic
expansion valve
box power supply
and communication
indoor power
Must connect electronic expansion valve box
NOTE
:
power and communication from corresponding
1PH.220-230V~.50Hz
indoor,wiring sequence must correspond with
the label respectively,other wise, will cause
PCB of indoor and electronic expansion valve
box not work and damaged.
BL
BL
1 2 3
CN8
CN17
CN23
CN25
CN18
FUSE
CN22
T3.15A/250VAC
RL2
RL1
CN12
CN19
CN20
CN3
1
1
3 2
3
2
1 2
B
R
R
M
M
swing motor
resumable heat
protector
80
10A/250VAC
℃,
FUSE
T15A/250VAC
one-off heat protector
105 ℃
10A/250VAC
,
only applicable for unit with
auxiliary electric heater
-115-
0010573324
NOTE:The dashed "
PCB inner wiring.
About control board outer connector:
In the diagram,gas pipe temp. sensor,liquid pipe
temp. sensor,indoor fan motor,transformer are
necessary parts
display,electronic expansion valve,float
switch,pump motor,swing motor are parts matched
with the model(combined usage
electric heater,negative ion generator,high voltage
accumulator are optional parts for health and
comfort
(
combination usage arbitrarily).Wired
controller and receive display only can choose one
transformer
at will.
The unit with remote controller is matched with
receive display:
1.Ceiling concealed type:CN11 must be short
BR
connected with a jump wire
2.Duct type
pump motor
W
3.Cassette type:connected with float switch
pump motor and swing motor
4.Cabinet type:CN11 must be short connected
with a jump wire
The unit with wired controller(equipped with wired
controller
,
can make remote operation on wired
controller with remote controller such as YR-H39)
Short connect CN15
wire
,
other parts are the same as remote control unit
Setting method with electronic expansion valve outside:
CN23 is disconnected,CN25 is connected with electronic
expansion valve communication,and the electronic
expansion valve box(MP3 or MP2) control indoor
refrigerant flow.
Setting method with built-in electronic expansion valve:
CN23 is short connected with a jump wire, CN6 is
connected with electronic expansion valve
indoor unit control refrigerant flow itself.
Attentions: The water temp sensor (CN9) and indoor
temp sensor (CN24) are unuseful now. The fourth bit
of 4 position dial switch is used to choose the
different speed of indoor fan under heating mode.
"ON" means that the speed of indoor can be choosed
from middle and low."OFF" means that the speed of
indoor fan can be choosed from high,middle and low.
auxiliary heater
short connector for built-in
CN
23
electronic expansion valve
CN15
short connector for wired
CN17
controller
serial communication port
CN16
connector for float switch
CN11
LED3
indicator
(
running
indicator
(
timer
-
LED2
LED1
indicator
(
power
---
"in indoor controll board is
Wired controller,receive
;
);
Auxiliary
;
:
connected with float switch and
;
、
;
,
connected with swing motor
;
:
CN17 together with jump
、
:
,
and
emergency switch(ON/OFF)
SW1
indoor fan motor low-speed relay
RL7
RL6
indoor fan motor Mid-speed relay
RL5
indoor fan motor High-speed relay
health function module relay
RL4
-
red
)
RL3
pump motor relay
yellow
)
RL2
swing motor relay
-
green
)
RL1
auxiliary eletric heater relay