6. Discharging temperature protection

11 flashes of outdoor ALARM light; fault readout: 11
When is temperature protection activated: Temperature of
discharge line is above 115° C.
Are stop valves in gas pipe and liquid
pipe of outdoor unit open totally?
yes
Does EEV work properly during heating cycle?
Check 1) Connector 2) Winding resistance 3)
Valve 4) Mainboard
yes
Is actual discharging temperature detected
by thermometer too high?
yes
Does indoor fan work properly during heating
cycle? Does outdoor fan work properly during
cooling cycle?
yes
Is filter or heat exchanger dirty?
no
Measure balance pressure and running
pressure to see if the refrigerant is too much or
lack. Is there air in system? Is there a leak?
no
Is piping twisted or deformed? Is piping
clogged with weld?
no
When TD is high, is refrigerant injection
circuit in good condition? Is injection
capillary in good condition?
no
1.Check coil and valve body of
electromagnetic valve.
2.Check injection capillary.
no
Open the stop valve
no
Repair outdoor EEV
no
Is discharging temperature
sensor in good condition?
yes
replace PCB
no
Check fan motor and capacitor
yes
cleaning
yes
Conduct leak test.
Evacuate and recharge
yes
Adjustment or
replacement
-167-
>a__WcU[S^ <[c >a`V[e[a`Wc
no
Replace TD sensor