Fujitsu WOxK112LCT Design & Technical Manual page 59

High power series (3 phase type) air to water split type
Table of Contents

Advertisement

ACCESS
LINE
LEVEL
2056
U
2803
S
2843
S
2844
S
2862
S
2873
S
2882
S
2884
S
2886
S
2916
S
2920
S
3700
S
3701
S
3705
S
3720
S
3723
5024
S
5030
S
5055
S
5057
S
5061
S
5093
S
FUNCTION
Swimming pool
Setpoint source heating
Heat pump
Overrun time cond pump
Compressor off time min
Switch-off temp max
Locking time stage 2
Compressor mod run time
Release integral electric flow
Release electric flow below OT
Compensation heat deficit
Max setpoint HP DHW charg
With electrical utility lock
Supplementary source
Release below outside temp
Release above outside temp
Overrun time
Switching integral (for boiler relief)
Locking time
DHW storage tank
Switching differential
Charging time limitation
Recooling temp
Recooling collector
Electric immersion heater release
Not used
- (CS01 - 14) -
- (CS01 - 14) -
SETTING RANGE
OR DISPLAY
8.0...80.0°C
0...240s
0...120min
8...100°C
0...40min
10...240s
0...500°Cmin
---, -30...30°C
Off
On
Only with
floor curing fct
---, 8... 80°C
Locked / Release
---, -50...50°C
---, -50...50°C
0...120min
0...500°Cmin
0...120min
0...20°C
---, 10...600min
8...95°C
Off
Summer
Always
24h/day
DHW release
Time program 4/DHW
FACTORY
SETTING
22.0°C
240s
8min
75°C
5min
240s
100°Cmin
2°C
Off
60°C
Released
2.0°C
20min
100°Cmin
30min
7°C
90min
65°C
Summer
DHW release
Control system