Operator Key Definitions
(Continued)
System Initialization
(Power-Up)
NORMAL POWER-UP CONDITIONS
A p p l y s y s t e m p o w e r t o t h e 4 0 0 4 p a n e l .
T h e p a n e l d i s p l a y s a n d i n d i c a t o r s a p p e a r .
T h e t o n e a l e r t s o u n d s f o r o n e
s e c o n d a n d t h e u s e r i n t e r f a c e
p a n e l " A C P O W E R " L E D i s O N .
P r o g r a m t h e 4 0 0 4 f o r y o u r d e s i r e d
s y s t e m c o n f i g u r a t i o n ( S e e C h a p t e r
2 – " P r o g r a m m i n g I n s t r u c t i o n s " ) .
The "ACK" key is also used to perform a lamp test on the system LEDs and
displays. When the "ACK" key is pressed for five seconds, the red and
yellow, seven-segment displays (all segments), System tone-alert and Power
On, Alarm Silenced, and Supervisory LEDs turn ON and remain ON until
the "ACK" key is released.
8.
Alarm Silence Key - The "ALARM SILENCE" key de-energizes NACs
configured as "On Until Silence." The "ALARM SILENCED" LED turns
ON and remains ON until all alarms are cleared.
Follow the flow chart below to initialize the 4004 FACP.
IMPORTANT: Notify appropriate personnel (building occupants, fire
T h e t o n e a l e r t s o u n d s c o n t i n u o u s l y a n d
p r e s s i n g t h e " A C K " k e y i n d i c a t e s a
s y s t e m S u p e r v i s o r y , T r o u b l e , o r A l a r m
o n t h e r e d o r y e l l o w d i s p l a y s .
C h e c k F i e l d W i r i n g D i a g r a m 8 4 1 - 9 9 2 .
Make sure that power is removed
from the panel and the appropriate
circuit is disconnected from the
panel when checking the circuit.
I f , a f t e r c h e c k i n g
I f t h e s y s t e m s t i l l
c i r c u i t s , t h e S y s t e m
i n d i c a t e s c o n d i t i o n s
o n t h e r e d o r y e l l o w
a p p e a r s O K .
d i s p l a y s a f t e r f i e l d
w i r i n g c h e c k s ,
c o n t a c t y o u r l o c a l
R e a p p l y p o w e r t o
S i m p l e x B r a n c h
t h e S y s t e m .
O f f i c e ( l i s t e d i n t h e
Y e l l o w P a g e s u n d e r
F i r e A l a r m ) .
department and/or monitoring facility, etc.) of power-up.
POWER-UP TROUBLE CONDITIONS
T h e p a n e l d i s p l a y s a n d i n d i c a t o r s D O N O T a p p e a r .
F u s e s m a y h a v e o p e n e d o r a c i r c u i t b r e a k e r m a y
h a v e t r i p p e d .
Make sure power is removed from the panel and
appropriate circuit is disconnected from the
panel and when checking the system.
I f , a f t e r c h e c k i n g f u s e s a n d / o r
c i r c u i t s , t h e S y s t e m a p p e a r s
O K .
R e a p p l y p o w e r t o t h e
S y s t e m .
4-3
A p p l y s y s t e m p o w e r t o t h e 4 0 0 4 p a n e l .
I f a f u s e c o n t i n u e s t o o p e n o r
c i r c u i t b r e a k e r c o n t i n u e s t o
t r i p , c o n t a c t y o u r l o c a l
S i m p l e x B r a n c h O f f i c e ( l i s t e d
i n t h e Y e l l o w P a g e s u n d e r
F i r e A l a r m ) .