Toshiba RAV-SM564UTP-E Service Manual page 62

Hide thumbs Also See for RAV-SM564UTP-E:
Table of Contents

Advertisement

Setting 4-way cassette Indoor Unit model only
1. Using the set temperature
2. Using the timer time
SET
• Push
button. (The setting completes if the setting data are displayed.)
Connector (CN504)
for drain pump
CN34
SW501
(Red)
J01
[3] Writing the setting data to EEPROM
The settings stored in the EEPROM of the P .C. board for indoor unit servicing are the factory-set values.
SET
CL
Step 1
Push
,
and
∗ In the group control operation, the unit No. displayed for the first time is the header unit No.
At this time, the CODE No. (DN) shows "
and the swing operation starts if it has the louvers.
(The unit No. "
Step 2
Every time when
are displayed in order.
(The settings stored in the EEPROM of the P .C. board for indoor unit servicing are the factory-set values.)
Specify the indoor unit No. with its P .C. board replaced to the P .C. board for indoor unit servicing.
(You cannot perform this operation if "
Step 3
Select the CODE No. (DN) can be selected by pushing the
• Set the indoor unit type and capacity.
The factory-set values shall be written to the EEPROM by changing
the type and capacity.
1. Set the CODE No. (DN) to "
2. Select the type by pushing
(For example, 4-way Air Cassette Type is set to "0001".
Refer to table 2)
SET
3. Push
button.
(The operation completes if the setting data is displayed.)
4. Change the CODE No. (DN) to "
buttons for the temperature setting.
5. Select the capacity by pushing
(For example, 80 Type is set to "0012". Refer to table 3)
SET
6. Push
button.
(The setting completes if the setting data are displayed.)
/
/
buttons, set the data. (0001)
If the plug for short-circuit is attached on the P.C. board
before replacement, attach it on the P.C. board replaced.
J02
TEST
buttons on the remote controller simultaneously for more than 4 seconds.
" is displayed if the auto-address setting mode is interrupted in [2] step 2 a))
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. in the group control operation
". (without change)
/
buttons for the timer setting.
" by pushing
/
buttons, set "
" to the CODE No. (DN).
CAUTION
Be sure to set the jumper wire since the motor
protection level setting selection is performed on it.
∗ Set J02 as follows depending on the capacity class.
Type
4-Way Cassette
". Also, the fan of the indoor unit selected starts its operation
" is displayed.)
/
/
buttons for the timer setting.
– 62 –
FILE NO. SVM-13010
Jumper wire (J02)
SM56, 80
None
SM110, 140, 160
Required (factory setting)
button for the temperature setting.
<Fig. 1 RBC-AMT32E>
3 6 5 1
4 2