[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.
SET
CL
Step 1
Push
,
and
∗ When the group operation control is performed, the unit No. displayed for the first time is the header unit No.
At this time, the CODE No. (DN) shows "
and the swing operation also starts if it has the louvers.
Step 2
Every time when the
is displayed in order. Specify the indoor unit No. to be replaced.
setting. (this is the setting for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as shown
in the table 1 (example).
After writing down all setting data, push
(It takes approx. 1 min until the remote controller operation is available again.)
CODE No. required at least
DN
Contents
10
11
12
13
14
[2] P.C. Board for indoor unit servicing replacement procedures
Step 1
Replace the P .C. board to the P .C. board for indoor unit servicing.
At this time, perform the same setting of the jumper wire (J01) setting (cut), switch SW501, (short-circuit)
connector CN34 as the setting of the P .C. board before replacement.
Step 2
According to the system configuration, turn on the indoor unit following to the either methods shown below.
a) Single operation (Indoor unit is used as standalone.)
Turn on the indoor unit.
1. After completion of the auto-address setting mode (required time: approx. 5 min.), proceed to [3].
(System address = 1, Indoor unit address = 1, Group address = 0 (standalone) are automatically set.)
setting mode, and proceed to [3]. (The unit No. "
b) Group operation (including twin triple and double twin system)
Turn on the indoor unit(s) with its P .C. board replaced to the P .C. board for indoor unit servicing, accord-
ing to either methods 1 or 2 shown below.
1. Turn on only the indoor unit with its P .C. board replaced. (Be sure to confirm the remote controller is
surely connected. If not, the operation [3] cannot be performed.)
Perform either methods 1 or 2 described in item a) above.
2. Turn on the multiple indoor units including the indoor unit with its P .C. board replaced.
• Twin or triple or double twin 1 system only
• All group connections
After completion of the auto-address setting mode (required time: approx. 5 min.), proceed to [3].
∗ The header unit of the group may be changed by performing the auto-address setting.
Also, the system address/Indoor unit address of the indoor unit with its P .C. board replaced may be
assigned to the addresses (not used) other than those of the indoor units without its P .C. board replaced.
It is recommended to keep the information in advance, which cooling system the indoor unit belongs to
or whether the indoor unit works as the header unit or the follower unit in the group control operation.
TEST
button on the remote controller simultaneously for more than 4 seconds.
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. under the group control
1. The CODE No. for the Indoor unit type and Indoor unit capacity are
required to set the rotation number setting of the fan.
2. If the system/indoor/group addresses are different from those before
replacement, the auto-address setting mode starts and the manual
resetting may be required again.
(when the multiple units group operation including twin system.)
CL
TEST
,
and
buttons simultaneously for more than 4 seconds to interrupt the auto-address
". Also, the fan of the indoor unit selected starts its operation
by pushing
/
/
buttons for the temperature setting.
" to "
". The CODE No. (DN) may skip.
button to return to the normal stop status.
" is displayed.)
- 61 -