Toshiba RAV-SM564UTP-E Service Manual page 36

Hide thumbs Also See for RAV-SM564UTP-E:
Table of Contents

Advertisement

No.
Item
19
DC motor
20
Self-clean operation
(Dry operation)
21
Save operation
Outline of specifications
1) When the fan operation has started, positioning of the
stator and the rotor are performed.
(Moves slightly with tap sound)
2) The motor operates according to the command from the
indoor controller.
Notes)
• When the fan rotates while the air conditioner stops due to
entering of outside air, etc, the air conditioner may operate
while the fan motor stops.
• When a fan lock is found, the air conditioner stops, and an
error is displayed.
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following
three self-clean operations are performed.
Compressor
Self-clean
ON period
operation period
0 to 10 min.
None
10 to 60 min.
1 hour
60 min. to
2 hours
2) During operation of self-clean,
remote controller screen. However the operation lamp
(Green LED) goes off.
3) To stop the self-clean operation, push twice the
[ON/OFF] button on the remote controller continuously.
(Stop the operation as compressor ON time in the table
above: 10 minutes or below.)
4) When the follower unit executes self-clean operation in the
group connection, the segment of
wired remote controller screen via master unit.
∗ If self-clean operation is not used, set invalidity
(does not use) of the self-clean operation by changing
[0001 (At shipment) of CODE No. (DN) [D3] to [0000].
∗ To erase the
display during operation of self-clean,
change CODE No. [D4] from [0000: Display
(At shipment)] to [0001: Non-display].
SAVE
1) Turn on
button on the remote controller.
2) During operation of save operation,
wired remote controller.
3) During save operation, the current release control is
performed with the restriction ratio set in EEPROM on
the outdoor unit.
4) The restriction ratio can be set by keeping
pushed for 4 seconds or more on the remote controller.
5) When validating the save operation, the next operation
starts with save operation valid because contents are
held even when operation stops, operation mode
changes or power supply is reset.
6) The restriction ratio can be set by changing the setup
data of CODE No. (DN) [C2] in the range of 50 to 100%
(every 1%, Setting at shipment: 75%).
– 36 –
FAN
Drain pump
Fan only
STOP
Horizontal discharge position
(UL)
lights on the wired
is displayed on the
SAVE
lights on the
SAVE
button
FILE NO. SVM-13010
Remarks
Check code [P12]
Louver
It is recognized as
[STOP] from the
remote monitor side.
Carry out setting
operation during stop of
the unit; otherwise the
unit stops operation.
For the setup opera-
tion, refer to "How to
set up contents of
save operation" of
Installation Manual.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents