4-4-5. Indoor Unit Installation

1. Carefully remove the indoor unit from the
packing case and pull out the shipping block on
the motor of the unit.
Shipping
block
2. Place the pattern sheet on the ceiling at the spot
where you want to install the indoor unit.
Note : • Since the diagram is made of paper, it may
shrink or stretch slightly due to temperature or
humidity. For this reason, before drilling the
holes maintain the correct dimensions between
the markings.
3. Insert bolt anchors. Use existing ceiling
supports or construct a suitable support as
shown in figure.
Concrete
Hole in anchor
Hole in plug
Suspension bolt(M8)-field supply
4. Install the suspension bolts depending on the
ceiling type.
IMPORTANT : Ensure that the ceiling is strong enough
to support the weight of the indoor unit.
Before hanging the unit, test the strength of each
attached suspension bolt.
Samsung Electronics
Insert
Ceiling support
5. Screw eight nuts to the suspension bolts making
space for hanging the indoor unit.
IMPORTANT : You must install the suspension bolts
more than four when installing the indoor unit.
6. Hang the indoor unit to the suspension bolts
between two nuts.
Note : • Tubing must be laid and connected inside the
ceiling when suspending the unit. If the ceiling
is already constructed, lay the tubing into
position for connection to the unit before
placing the unit inside the ceiling.
7. Screw the nuts to suspend the unit.
8. Adjust level of the unit by using measurement
plate for all 4 sides.
Note : • For proper drainage of condensate, give a
slightly slant to the left or right side of the unit
which will be connected with the drain hose.
But if you would like to install a drain pump,
make the base pan be level with the ceiling.
For proper drainage of condensate,
give a 3mm slant to the left or right
side of the unit which will be
connected with the drain hose, as
shown in the figure. Make a tilt when
you wish to install the drain pump, too.
When the drain hose is installed to the
right.
3mm
Installation
Drain tube outlet
4-21