4-4 Selecting Area for Installation

Select an area for installation that is suitable to
the customer's needs.

4-4-1 Indoor Unit

1. Make sure that you install the indoor unit in an
area providing good ventilation. It must not be
blocked by an obstacle affecting the airflow near
the air inlet or the air outlet.
2. Make sure that you install the indoor unit in an
area allowing good air handling and endurance
of vibration of the indoor unit.
3. Make sure that you install the indoor unit in an
area where there is no source of heat or vapor
nearby or direct sunlight.
4. Make sure that you install the indoor unit in an
area from which hot or cool air will spread
evenly in the room.
5. Make sure that you install the indoor unit in an
area that provides easy pipe connection with
the outdoor unit, and easy drainage for
condensed water.
Space requirement when installing the indoor unit
Electrical component box
250mm
400mm
air outlet duct flange
Space requirement when installing the air filter
Note :
The air filter can be installed to the bottom or
rear of the indoor unit.
Samsung Electronics
Inspection
1256mm
access
450X450
650mm
Refrigerant
connection port
Rear of the indoor unit
165mm
6. The ceiling should not be inclined by more than
2 degrees.
7. The distance between the indoor unit and the
outdoor unit should not be longer than 30m.
(recommended distance between two units is 5m.).
and the height difference between the indoor unit
and the outdoor unit should be less than 15m.
8. There should be enough space around the indoor
unit to provide easy installation and service.
10. Please use the given accessories to install the
indoor unit. (set of slings)
• Check that the installed location is strong
enough to hang the indoor unit on.
• The distances of the following should be
limited:
The lengths of refrigerant tube 30 m.
The height difference between indoor and
outdoor unit should be less than 15 m.
You must have 5mm or more space between the
ceiling and the bottom of indoor unit. Otherwise, the
noice from the vibration of indoor unit may bother
the user.