Mitsubishi Electric City Multi PKFY-P06NAMU-E Technical & Service Manual page 12

Split-type, heat pump air conditioners
Table of Contents

Advertisement

4-2. ELECTRICAL PARTS SPECIFICATIONS
PKFY-P06NAMU-E
PKFY-P08NAMU-E
Model
Parts name
Room temperature
thermistor
Liquid pipe temperature thermistor
Gas pipe temperature thermistor
Fuse
(Indoor power board)
Fan motor
(with thermal fuse)
Fan motor capacitor
Vane motor
(with limit switch)
Linear expansion valve
Power supply terminal
block
Transmission terminal
block
Symbol
TH21
Resistance 30°F/15.8k , 50°F/9.6k , 70°F/6.0k , 80°F/4.8k , 90°F/3.9k , 100°F/3.2k
TH22
Resistance 30°F/15.8k , 50°F/9.6k , 70°F/6.0k , 80°F/4.8k , 90°F/3.9k , 100°F/3.2k
TH23
Resistance 30°F/15.8k , 50°F/9.6k , 70°F/6.0k , 80°F/4.8k , 90°F/3.9k , 100°F/3.2k
FUSE
MF
C
MV
LEV
TB2
TB5
PKFY-P06/P08NAMU-E
250V 6A
4-Pole Output 8W / PS4N8-KA
1.2μF × 440V
MSFBC20A03 DC12V
DC12V Stepping motor drive
Port dimension 3.2 (0~2000pulse) EDM-40YGME
(L1, L2,GR) 250V 20A
(M1, M2) 250V 10A
12