Job Name:
Drawing Reference:
System No.:
GENERAL FEATURES
• R410A refrigerant
• Seven sizes from 6,000 to 30,000 Btu/h
• Powerful airflow (CFM)
• Compact, lightweight, shiny-white, flat-panel design
• Quiet operation
• Multiple fan-speed settings
• Intake grille filter is easily removed for cleaning
• Built-in receiver is standard
• IT Terminal plug
SPECIFICATIONS
Capacity*
Cooling........................................................8,000 Btu/h
Heating........................................................9,000 Btu/h
Power
Power Source............................208 / 230V, 1-phase, 60Hz
Power Consumption
Cooling.............................................................0.03 kW
Heating.............................................................0.03 kW
Current
Cooling........................................................................0.30 A
Heating........................................................................0.30 A
Minimum Circuit Ampacity (MCA).................................0.38 A
Maximum Overcurrent Protection (MOCP) Fuse.................15 A
External Finish...............................Munsell No. 1.0Y 9.2 / 0.2
External Dimensions
Inches.................................11-5/8 H x 35-3/8 W x 9-13/16 D
mm..............................................295 H x 989 W x 249 D
Notes:
PKFY-P08NHMU-E2
Model:
Location:
Schedule No.
Date:
Net Weight
Unit...........................................................29 lbs. / 13 kg
Coil Type.................................................................Cross Fin
Fan
Type x Quantity...................................Line Flow Fan x 1
Airflow Rate (Low-Mid1-High)......................320 - 370 - 423 CFM
Motor
Type....................................One-phase Induction Motor
Output...........................................................0.030 kW
Air Filter....................................Polypropylene Honeycomb
Refrigerant Piping Dimensions
Liquid (High Pressure).....................1/4" / 6.35 mm (Flare)
Gas (Low Pressure).......................1/2" / 12.7 mm (Flare)
Drainpipe Dimension..................................I.D. 5/8" / 16 mm
Sound Pressure Levels
Low-Mid1-Mid2-High.............................34 - 39 - 43 dB(A)
OPTIONS
□ External Heat Adapter................................PAC-YU25HT
* Cooling / Heating capacity indicated at the maximum value at
operation under the following conditions:
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F
(35°C) DB
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C) WB
Note: Ventilation air: Providing sufficient ventilation air is an impor-
tant part of every building design. ASHRAE Standard 62 provides
the minimum ventilation air requirement. Also, check local codes.
(Aluminum Plate Fin and Copper Tube)
Need help?
Do you have a question about the PKFY-P08NHMU-E2 and is the answer not in the manual?
Questions and answers
HAS 5 HEADS & OTHER FOUR UNIT WORKS FINE FIFTH HEAD ALSO WORK BUT THERMOSTAT DISPLAY NOT WORKING, WHATS THE REASON FOR THAT? 12V VOLTAGE PRACENSE ON THERMOSTAT BUT DISPLAY NOT WORKS
If the thermostat display on the Mitsubishi Electric PKFY-P08NHMU-E2 unit is not working despite the presence of 12V voltage, possible reasons could include:
1. Faulty indoor controller board – The voltage may be present, but the board may not be processing or sending signals correctly.
2. Faulty display or remote controller – The display unit itself may be damaged or disconnected.
3. Incorrect dip switch settings – Misconfigured switches may prevent proper operation.
4. Malfunction in communication lines – There may be a break or fault in the wiring between the display and controller.
Check the indoor controller board and remote controller for faults, and verify dip switch settings.
This answer is automatically generated