Mitsubishi Electric PEHD-P1.6EAH Technical & Service Manual

Split-type, heat pump air conditioners

Advertisement

SPLIT-TYPE, HEAT PUMP
AIR CONDITIONERS
TECHNICAL & SERVICE MANUAL
Series PEHD / PEAD
<indoor unit> Service ref.
Models
PEHD-P1.6EAH
PEHD-P2EAH
PEHD-P2.5EAH
PEHD-P3EAH
PEHD-P4EAH
PEHD-P5EAH
PEHD-P6EAH
INDOOR UNIT
PEAD-P1.6EA
PEAD-P2EA
PEAD-P2.5EA
PEAD-P3EA
PEAD-P4EA
PEAD-P5EA
PEAD-P6EA
ON/OFF
TEMP.
REMOTE CONTROLLER
R407C
This manual does not cover the
following outdoor units. When
servicing them, please refer to
the service manual No.OC180
REVISED EDITION-A and this
manual as a set.
CONTENTS
2. SAFETY PRECAUTION ···························· 2
3. PART NAMES AND FUNCTIONS ············· 4
4. SPECIFICATION ······································· 7
5. DATA ························································ 15
7. OUTLINES & DIMENSIONS ···················· 37
8. WIRING DIAGRAM ·································· 39
9. DISASSEMBLY INSTRUCTIONS ············ 40
10. PARTS LIST ············································· 42
11. OPTIONAL PARTS ·································· 49
2004
PUH-P1.6VGA PU-P1.6VGA
PUH-P1.6YGA PUH-P2VGA
PU-P2VGA
PUH-P2YGA
PUH-P2.5VGA
PU-P2.5VGA
1
PUH-P2.5YGA
1
PUH-P3VGA
PU-P3VGA
PUH-P3YGA
PU-P3YGA
PUH-P4YGA
PU-P4YGA
PUH-P5YGA
PU-P5YGA
PUH-P6YGA
PU-P6YGA
1
TM

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PEHD-P1.6EAH

  • Page 1: Table Of Contents

    This manual does not cover the following outdoor units. When servicing them, please refer to <indoor unit> Service ref. the service manual No.OC180 REVISED EDITION-A and this Models PEHD-P1.6EAH PEAD-P1.6EA manual as a set. PEHD-P2EAH PEAD-P2EA PUH-P1.6VGA PU-P1.6VGA PUH-P1.6YGA PUH-P2VGA PEHD-P2.5EAH...
  • Page 2: Combination Of Indoor And Outdoor Units

    Cooling only type Indoor unit PUH-P · VGA / YGA PU-P · VGA / YGA 1.6VGA 1.6YGA 2VGA 2YGA 2.5VGA 2.5YGA 1.6VGA 2VGA 2.5VGA PEHD-P1.6EAH — — — — — — — Heat pump with PEHD-P2EAH — — — —...
  • Page 3: Safety Precaution

    SAFETY PRECAUTION Cautions for using with the outdoor unit which adopts R407C refrigerant. • Do not use the existing refrigerant piping. - The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrig- erant oil of the new unit to deteriorate.
  • Page 4 [1] Service tools Use the below service tools as exclusive tools for R407C refrigerant. Tool name Specifications Gauge manifold · Only for R407C. · Use the existing fitting SPECIFICATIONS. (UNF7/16) · Use high-tension side pressure of 3.43MPa·G or over. Charge hose ·...
  • Page 5: Part Names And Functions

    PART NAMES AND FUNCTIONS Indoor Unit Air intake (sucks the air inside the room into the unit) Air outlet In case of rear inlet In case of bottom inlet (Only 1.6~2.5HP)
  • Page 6 Remote controller Once the operation of the unit is set, subsequent operations can be performed only by pressing the ON/OFF button repeatedly. Operation buttons 1Hr. CENTRALLY CONTROLLED ON OFF ˚C CLOCK CHECK FILTER CHECK MODE ˚C TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE...
  • Page 7 Display CENTRALLY CONTROLLED 1Hr. ON OFF ˚C CLOCK CHECK FILTER CHECK MODE ˚C TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE DEFROST TEMP. ON/OFF IKLJ A Current time/Timer K Not available function B Centralized control L Ventilation C Timer ON M Function setting mode D Abnormality occurs N Test run mode...
  • Page 8: Specification

    SPECIFICATION 1. Heat pump type Rating Conditions (ISO T1) Service Ref. With Electric heater PEHD-P1.6EAH PEHD-P2EAH Item Without Electric heater PEAD-P1.6EA PEAD-P2EA Function Cooling Heating Cooling Heating Btu/h 15,300 16,700 (20,100) 18,900 21,000 (24,400) Capacity 4,500 4,900 (5,900) 5,550 6,150 (7,150) Total input 1.75...
  • Page 9 Rating Conditions (ISO T1) Service Ref. With Electric heater PEHD-P2.5EAH Item Without Electric heater PEAD-P2.5EA Function Cooling Heating Btu/h 22,800 24,500 (29,700) Capacity 6,700 7,200 (8,700) Total input 2.68 2.45 (3.95) With Electric heater PEHD-P2.5EAH Service Ref. Without Electric heater PEAD-P2.5EA Power supply Single phase,50Hz,220-240V...
  • Page 10 Rating Conditions (ISO T1) Service Ref. With Electric heater PEHD-P3EAH PEHD-P4EAH Item Without Electric heater PEAD-P3EA PEAD-P4EA Function Cooling Heating Cooling Heating Btu/h 26,300 31,000 (38,200) 33,100 35,500 (43,700) Capacity 7,700 9,100 (11,200) 9,700 10,400 (12,800) Total input 3.41 3.24 (5.34) 3.90 4.07 (6.47) With Electric heater...
  • Page 11 Rating Conditions (ISO T1) Service Ref. With Electric heater PEHD-P5EAH PEHD-P6EAH Item Without Electric heater PEAD-P5EA PEAD-P6EA Function Cooling Heating Cooling Heating Btu/h 42,000 47,400 (57,700) 48,100 57,000 (67,200) Capacity 12,300 13,900 (16,900) 14,100 16,700 (19,700) Total input 4.93 4.81 (7.81) 5.90 5.96 (8.96) With Electric heater...
  • Page 12 2. Cooling only type Rating Conditions (ISO T1) Service Ref. PEAD-P1.6EA PEAD-P2EA Item Function Cooling Cooling Btu/h 15,300 18,900 Capacity 4,500 5,550 Total input 1.75 2.44 Service Ref. PEAD-P1.6EA PEAD-P2EA Power supply Single phase,50Hz,220-240V Input 0.13 0.15 Running current 0.55 0.63 Starting current –...
  • Page 13 Rating Conditions (ISO T1) Service Ref. PEAD-P2.5EA Item Function Cooling Btu/h 22,800 Capacity 6,700 Total input 2.68 Service Ref. PEAD-P2.5EA Power supply Single phase,50Hz,220-240V Input 0.17 Running current 0.72 Starting current – External finish Galvanized sheets Heat exchanger Plate fin coil Fan (drive) ×...
  • Page 14 Rating Conditions (ISO T1) Service Ref. PEAD-P3EA PEAD-P4EA Item Function Cooling Cooling Btu/h 26,300 33,100 Capacity 7,700 9,700 Total input 3.41 3.90 Service Ref. PEAD-P3EA PEAD-P4EA Power supply Single phase,50Hz,220-240V Input 0.40 0.62 Running current 1.70 2.64 Starting current – –...
  • Page 15 Rating Conditions (ISO T1) Service Ref. PEAD-P5EA PEAD-P6EA Item Function Cooling Cooling Btu/h 42,000 48,100 Capacity 12,300 14,100 Total input 4.93 5.90 Service Ref. PEAD-P5EA PEAD-P6EA Power supply Single phase,50Hz,220-240V Input 0.64 0.66 Running current 2.72 2.79 Starting current – –...
  • Page 16: Data

    DATA 1. PERFORMANCE DATA 1) COOLING CAPACITY <1> PEHD-P1.6EAH/PEAD-P1.6EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) SHF P.C. SHC(W) SHF P.C. SHC(W) SHF P.C. 4455 2762 0.62 1.40 4320 2678 0.62 1.48...
  • Page 17 PEHD-P2EAH/PEAD-P2EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) SHF P.C. SHC(W) P.C. SHC(W) SHF P.C. 5495 3501 0.64 1.95 5328 3395 0.64 2.06 5162 3289 0.64 2.18 5883 3023 0.51 1.99 5717 2938 0.51...
  • Page 18 PEHD-P2.5EAH/PEAD-P2.5EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) SHF P.C. SHC(W) SHF P.C. SHC(W) SHF P.C. 6633 4055 0.61 2.14 6432 3932 0.61 2.26 6231 3810 0.61 2.40 7102 3502 0.49 2.19 6901 3403...
  • Page 19 PEHD-P3EAH/PEAD-P3EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) SHF P.C. SHC(W) P.C. SHC(W) SHF P.C. 7623 5120 0.67 2.72 7392 4965 0.67 2.88 7161 4810 0.67 3.05 8162 4421 0.54 2.78 7931 4296 0.54...
  • Page 20 PEHD-P4EAH/PEAD-P4EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) SHF P.C. SHC(W) SHF P.C. SHC(W) SHF P.C. 9603 6202 0.65 3.12 9312 6014 0.65 3.29 9021 5826 0.65 3.49 10282 5355 0.52 3.18 9991 5204...
  • Page 21 PEHD-P5EAH/PEAD-P5EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) SHF P.C. SHC(W) P.C. SHC(W) SHF P.C. 12177 8179 0.67 3.94 11808 7931 0.67 4.17 11439 7683 0.67 4.41 13038 7062 0.54 4.02 12669 6862 0.54...
  • Page 22 PEHD-P6EAH/PEAD-P6EA Outdoor intake air D.B. (°C) Indoor Indoor Intake air Intake air D.B. (°C) W.B. (°C) SHC(W) P.C. SHC(W) SHF P.C. SHC(W) SHF P.C. 13959 8895 0.64 4.71 13536 8625 0.64 4.98 13113 8356 0.64 5.27 14946 7681 0.51 4.81 14523 7463 0.51...
  • Page 23 Cooling capacity correction factors Refrigerant piping length (one way) Service Ref. PEHD-P1.6EAH 1.00 0.993 0.984 0.978 0.969 0.961 0.956 0.948 – – PEAD-P1.6EA PEHD-P2EAH 1.00 0.993 0.984 0.978 0.969 0.961 0.956 0.948 – – PEAD-P2EA PEHD-P2.5EAH 1.00 0.989 0.980 0.970 0.960...
  • Page 24: Heating Capacity Correction Factors

    11690 5.24 15364 6.14 17702 6.88 19706 7.42 Note CA: Capacity (W) P.C.: Power consumption (kW) Heating capacity correction factors Refrigerant piping length (one way) Service Ref. PEHD-P1.6EAH 1.00 0.998 0.995 0.993 0.990 0.988 0.985 0.983 – – PEAD-P1.6EA PEHD-P2EAH 1.00...
  • Page 25 Heating Correcting the capacity line influenced by frosting. Not correcting the capacity line influenced by frosting. INDOOR D.B. (°C) INDOOR D.B. (°C) -12 -10 OUTDOOR W.B. (°C)
  • Page 26 2 . FAN PERFORMANCE AND CORRECTED AIR FLOW PEHD-P1.6EAH, PEAD-P1.6EA Capacity Corrected Air Flow input Fan Performance <30Pa> Cooling Air flow (CMM) 10 12 14 16 Air Flow (CMM) Heating Fan Performance <70Pa> 12 14 16 Air flow (CMM) 10 12...
  • Page 27 PEHD-P2.5EAH, PEAD-P2.5EA Capacity Fan Performance <30Pa> Corrected Air Flow input Cooling 12 14 16 24 26 Air flow (CMM) 10 12 14 16 18 20 22 24 Air Flow (CMM) Heating Fan Performance <70Pa> 12 14 16 22 24 Air flow (CMM) 10 12 14 16 18 20 22 24 26 Air Flow (CMM) PEHD-P3EAH, PEAD-P3EA...
  • Page 28 PEHD-P4EAH, PEAD-P4EA Fan performance <130pa> Fan performance <70pa> Recommended range Recommended range 26 28 30 32 34 36 38 40 24 26 28 30 32 34 36 38 Ai r flo w (CMM ) A i r fl o w ( C MM ) Corrected Air Flow Heating Capacity...
  • Page 29 PEHD-P6EAH, PEAD-P6EA Fan performance <70pa> Fan performance <130pa> Recommended range Recommended range 36 38 40 42 44 46 48 50 52 36 38 40 42 44 46 48 50 A ir flow (CMM) Ai r fl ow (CM M) Heating Corrected Air Flow Capacity Input...
  • Page 30 3. ELECTRICAL DATA Heat pump type Rating Conditions (ISOT1) Indoor ..220V 50Hz 1 phase Outdoor ..220V/380V 50Hz 1/3 phase With heater PEHD-P1.6EAH PEHD-P2EAH PEHD-P2.5EAH Indoor Service unit Without heater PEAD-P1.6EA PEAD-P2EA PEAD-P2.5EA Ref. Outdoor unit PUH-P1.6VGA PUH-P1.6YGA PUH-P2VGA PUH-P2YGA PUH-P2.5VGA1...
  • Page 31 Indoor ..220V 50Hz 1 phase Outdoor ..220V/380V 50Hz 1/3 phase With heater PEHD-P3EAH PEHD-P4EAH PEHD-P5EAH PEHD-P6EAH Indoor Service unit Without heater PEAD-P3EA PEAD-P4EA PEAD-P5EA PEAD-P6EA Ref. Outdoor unit PUH-P3VGA PUH-P3YGA PUH-P4YGA PUH-P5YGA PUH-P6YGA Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating...
  • Page 32 Cooling only type Rating Conditions (ISOT1) Indoor ..220V 50Hz 1 phase Outdoor ..220V/380V 50Hz 1/3 phase PEAD- PEAD- Indoor unit PEAD-P2EA PEAD-P3EA PEAD-P4EA PEAD-P5EA PEAD-P6EA P1.6EA P2.5EA Service Ref. Outdoor unit PU-P2VGA PU-P3VGA PU-P3YGA PU-P4YGA PU-P5YGA PU-P6YGA P1.6VGA P2.5VGA1 Mode Cooling...
  • Page 33 4. STANDARD OPERATION DATA Heat pump type Rating Conditions (ISO T1) With Electric heater PEHD-P1.6EAH PEHD-P2EAH PEHD-P2.5EAH Service Ref. PEAD-P1.6EA PEAD-P2EA PEAD-P2EA Without Electric heater Mode Cooling Heating Cooling Heating Cooling Heating Capacity 4,500 4,900 5,550 6,150 6,700 7,200 Input 1.75...
  • Page 34 With Electric heater PEHD-P3EAH PEHD-P4EAH PEHD-P5EAH PEHD-P6EAH Service Ref. PEAD-P3EA PEAD-P4EA PEAD-P5EA PEAD-P6EA Without Electric heater Mode Cooling Heating Cooling Heating Cooling Heating Cooling Heating 9,100 10,400 13,900 16,700 Capacity 7,700 9,700 12,300 14,100 (11,200) (12,800) (16,900) (19,700) 3.24 4.07 4.81 5.96 Input...
  • Page 35 Cooling only type Rating Conditions (ISO T1) PEAD-P1.6EA PEAD-P2EA PEAD-P2.5EA Service Ref. Cooling Cooling Cooling Mode 4,500 5,550 6,700 Capacity 1.75 2.44 2.68 Input Indoor unit Service Ref. PEAD-P1.6EA PEAD-P2EA PEAD-P2.5EA Phase,Hz 1 , 50 1 , 50 1 , 50 Volts 0.55 0.63...
  • Page 36 PEAD-P3EA PEAD-P4EA PEAD-P5EA PEAD-P6EA Service Ref. Cooling Cooling Cooling Cooling Mode Capacity 7,700 9,700 12,300 14,100 Input 3.41 3.90 4.93 5.90 Indoor unit Service Ref. PEAD-P3EA PEAD-P4EA PEAD-P5EA PEAD-P6EA Phase,Hz 1 , 50 1 , 50 1 , 50 1 , 50 Volts Amperes 1.70...
  • Page 37: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM PEHD-P1.6, 2, 2.5, 3, 4, 5, 6EAH PEAD-P1.6, 2, 2.5, 3, 4, 5, 6EA Refrigerant flow in cooling Refrigerant flow in heating Indoor unit Indoor heat exchanger Strainer Thermistor Thermistor Distributor with strainer...
  • Page 38: Outlines & Dimensions

    OUTLINES & DIMENSIONS 1. INDOOR UNIT PEHD-P1.6, 2, 2.5EAH PEAD-P1.6, 2, 2.5EA Service space:500 or more 10-ø3(1.6,2HP) 12-ø3(2.5HP) 50~150 Model Access door P1.6,2 P2.5 1012 1070 1044 Lifting bolt hole (14×22) Refrigerant piping flare connection (liquid ø9.52 copper tube):HP Refrigerant piping flare connection (gas ø15.88 copper tube):LP Drain R1(External thread) Electrical parts box Electric Heater ···...
  • Page 39 2. REMOTE CONTROLLER (Front view) (Side view) (Rear view)
  • Page 40: Wiring Diagram

    WIRING DIAGRAM INDOOR UNIT CN2S(WHT) Optional parts External static OUTDOOR UNIT pressure 70Pa(7mmAq) DC14V <PEAD-P1.6·2·2.5EA,PEHD-P1.6·2·2.5EAH> <PU(H)-P3VGA> (Red) POWER SUPPLY ~(1PHASE) CONT.BOARD OUTDOOR 220~240V 50Hz CN02(WHT) CN01(BLU) DRAIN PUMP POWER 1 3 5 POWER CN03 CN2D (WHT) (BLU) (RED) (WHT) TRANSMISSION WIRE CN31 <PU(H)>...
  • Page 41: Disassembly Instructions

    DISASSEMBLY INSTRUCTIONS Figure1. Disconnect the fan motor connecter (and the booster heater connector) Drain catches (Hidden) Heat exchanger Bottom plate Filter assembly Drain catches (Hidden) Bottom plate Drain pan 1 1 . Removing the fan motor 1. Removing the 9 screws that fix the bottom plate A, 5.
  • Page 42 Figure3. Fan base Sirocco fan Booster heater Motor Housing Motor base assembly (Only PEHD-P3, Bush PEAD-P3) Bush Piece Sirocco fan Piece Housing assembly 2 2 . Removing the booster heater Figure4. 1. Remove the bottom plate, drain pan, and bottom plate assembly.
  • Page 43: Parts List

    PARTS LIST PEHD-P1.6EAH, PEAD-P1.6EA, PEHD-P2EAH, PEAD-P2EA PEHD-P2.5EAH, PEAD-P2.5EA, PEHD-P3EAH, PEAD-P3EA PEHD-P4EAH, PEAD-P4EA, PEHD-P5EAH, PEAD-P5EA PEHD-P6EAH, PEAD-P6EA EXTERNAL PARTS 5, 6 3, 4 9, 10 7, 8 Qt’y/set Part No. Part Name Drawing No. PEAD- PEHD- PEAD- PEHD- PEAD- Spec. PEHD- P1.6EA...
  • Page 44 7.8.9.10 4.5.6 14.15.16 11.12.13 1.2.3 Qt’y/set Part No. Part Name Drawing No. PEAD- PEHD- PEAD- PEHD- PEAD- Spec. PEHD- PEAD- PEHD- P3EA P3EHA P4EA P4EHA P5EA P5EHA P6EA P6EHA S70 041 669 Bottom plate 1 W634050Z01 S70 042 669 Bottom plate 1 W634028Z01 Bottom plate 1 W631101Z04...
  • Page 45 PEHD-P1.6EAH, PEAD-P1.6EA, PEHD-P2EAH, PEAD-P2EA PEHD-P2.5EAH, PEAD-P2.5EA, PEHD-P3EAH, PEAD-P3EA PEHD-P4EAH, PEAD-P4EA, PEHD-P5EAH, PEAD-P5EA PEHD-P6EAH, PEAD-P6EA 2, 3 BLOWER PARTS 5, 6 13, 14 9, 10, 11 7, 8 5, 6 7, 8 Qt’y/set Part No. Part Name Drawing No. PEAD- PEHD-...
  • Page 46 3.4.5 15.16.17 18.19 10.11.12 13.14 1.20 Qt’y/set Part No. Part Name Drawing No. PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- P3EA P3EHA P4EA P4EHA P5EA P5EHA P6EA P6EHA Piece R02K338H02 S70 508 131 Piece R02K338G82 with a nut S70 508 132 Fan base ass’y W634058G02 S70 073 677...
  • Page 47 PEHD-P1.6EAH, PEAD-P1.6EA, PEHD-P2EAH, PEAD-P2EA PEHD-P2.5EAH, PEAD-P2.5EA, PEHD-P3EAH, PEAD-P3EA PEHD-P4EAH, PEAD-P4EA, PEHD-P5EAH, PEAD-P5EA PEHD-P6EAH, PEAD-P6EA CONTROL BOX PARTS 11. 10. 9. 8 Qt’y/set Part No. Part Name Drawing No. Spec. PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- P1.6EA P1.6EAH P2EA P2EAH P2.5EA P2.5EAH...
  • Page 48 Qt’y/set Part No. Part Name Drawing No. Spec. PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- P3EA P3EHA P4EA P4EHA P5EA P5EHA P6EA P6EHA S70 979 317 Terminalbed P436110X01 < TB4 > Terminalbed BA73S950H02 < TB5 > S70 435 717 S70 E00 313 P.W.B DENGEN-E P718898X01...
  • Page 49: Electrical Parts

    PEHD-P1.6EAH, PEAD-P1.6EA, PEHD-P2EAH, PEAD-P2EA PEHD-P2.5EAH, PEAD-P2.5EA, PEHD-P3EAH, PEAD-P3EA PEHD-P4EAH, PEAD-P4EA, PEHD-P5EAH, PEAD-P5EA PEHD-P6EAH, PEAD-P6EA ELECTRICAL PARTS ON/OFF TEMP. Qt’y/set Part No. Part Name Drawing No. Spec. PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- PEAD- PEHD- P3EA P3EHA P4EA P4EHA P5EA P5EHA...
  • Page 50: Optional Parts

    OPTIONAL PARTS 1. REFRIGERANT PIPES Service Ref. : PEHD-P1.6,2,2.5,3EAH/PEAD-P1.6,2,2.5,3EA Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-E Pipe length Liquid : ø9.52 Gas : ø15.88 Pipe size O.D. Indoor unit : Flared Outdoor unit : Flared Connection method Service Ref. : PEHD-P4,5,6EAH/PEAD-P4,5,6EA Part No.
  • Page 51 7. OPTIONAL MOTOR The external static pressure of 130Pa allows long ducts to be used more extensively to enable the most convenient posi- tioning of indoor units. Part No. PAC-SK005MT-F PAC-SK004MT-F PAC-SK003MT-F Applied model PEHD-P3EAH/PEAD-P3EA PEHD-P4EAH/PEAD-P4EA PEHD-P5,6EAH/PEAD-P5,6EA 8. DRAIN WATER LIFT-UP MECHANISM This allows more versatility when selecting drain piping layouts.
  • Page 52 HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN MEE 01K048-A New publication, effective Dec. 2004 Issued in Dec. 2004 Specifications subject to change without notice. Printed in Japan...