Rating Conditions (ISO T1)
Service Ref. With Electric heater
Item
Function
Capacity
1
Total input
1
Service Ref.
Power supply
Input
Running current
Starting current
External finish
Heat exchanger
Fan (drive) × No.
Fan
Fan motor output
Airflow (Lo-Hi)
External static pressure
Booster heater
Operation control & Thermostat
Noise level (Lo-Hi)
Unit drain pipe O.D
Dimensions
With Electric heater
Weight
Without Electric heater
Service Ref.
Power supply
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan (drive) × No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D
Connection method
Between the indoor &
outdoor unit
Notes
1. Rating Conditions (ISO T1)
Cooling: Indoor:
D.B.27°C (80°F), W.B.19°C (66°F)
Outdoor: D.B.35°C (95°F), W.B.24°C (75°F)
Heating: Indoor:
D.B.20°C (68°F)
Outdoor: D.B.7°C (45°F), W.B.6°C (43°F)
Refrigerant piping length (one way): 5m (16ft)
3. Above data based on indicated voltage
Indoor Unit:
Single phase 240V 50Hz
Outdoor Unit: Single phase 240V 50Hz / 3 phase 415V 50Hz
Without Electric heater
Btu/h
W
kW
With Electric heater
Without Electric heater
2
kW
2
A
2
A
kW
3
m
/min (CFM)
Pa (mmAq)
2
kW
dB
mm (in.)
W
mm (in.)
D
mm (in.)
H
mm (in.)
kg (lbs)
kg (lbs)
kW
A
A
kW
W
kW
m
3
/min (CFM)
Cooling
dB
Heating
dB
W
mm (in.)
D
mm (in.)
H
mm (in.)
kg (lbs)
kg (lbs)
L
Liquid
mm (in.)
Gas
mm (in.)
Indoor side
Outdoor side
Height difference
Piping length
PEHD-P2.5EAH
PEAD-P2.5EA
Cooling
22,800
6,700
2.68
PEHD-P2.5EAH
PEAD-P2.5EA
Single phase,50Hz,220-240V
0.17
0.72
–
Galvanized sheets
Centrifugal (direct) × 2
0.116 (at 70 Pa)
17-21<600-741>
Built in remote controller
1,175 (46-1/8)
PUH-P2.5VGA/YGA
Single phase,50Hz,220-240V / 3 phase,50Hz,380-415V (4 wires)
2.51
11.27/4.11
Munsell 5Y 8/1
Linear Expansion Valve
NE41VMJM/NE41YEJM
VGA...Inner thermostat, HP switch, Discharge thermo.
YGA...Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
Propeller (direct) × 1
Reverse cycle
900 (35-7/16)
330+20 (13+3/4)
1.2 (Ester) MEL56
2. Guaranteed operating range
Upper limit
Cooling
Lower limi
Upper limit
Heating
Lower limi
Heating
24,500 (29,700)
7,200 (8,700)
2.45 (3.95)
0.17<1.67>
0.72<6.96>
–
Plate fin coil
30/70
<1.5>
37-41
32 (1-1/4)
700 (27-5/8)
295 (11-5/8)
44 (97)
42 (92)
2.28
10.32/4.03
77/32
Hermetic
1.9
Line start
38
Plate fin coil
0.070
50 (1,770)
48
50
855 (33-5/8)
82 (181)
R407C
3.3 (7.3)
9.52 (3/8)
15.88 (5/8)
Flared
Flared
Max.50m
Max.50m
Indoor
D.B.35°C, W.B.22.5°C
D.B.19°C, W.B.15°C
D.B.28°C
D.B.24°C, W.B.18°C
D.B.17°C
D.B.-11°C, W.B.-12°C
1 : ( ) Shows the total rating.
2 : < > Shows only the booster heater r ating.
Outdoor
D.B.46°C
D.B.-5°C