Clearances To Combustibles (Ul And Ulc); Hearth Extension - Quadra-Fire 31I-ACC Owner's Manual

Advanced combustion control (acc) wood insert installation and operation
Hide thumbs Also See for 31I-ACC:
Table of Contents

Advertisement

3100-I ACC Wood Insert
B. Clearances to Combustibles, United States and Canada (UL and ULC)
Minimum Clearances to Combustible Material
Masonry, Heat Exchanger & Zero
Clearance
MANTEL CLEARANCES
No Mantel Deflector
with Mantel Deflector
)
(Figure 30.1
FLOOR PROTECTION
Floor height 0" to 6-1/2"
(6 to 165mm) below Insert Base
Floor height greater thant 6-1/2"
(165mm) below Insert Base
THERMAL PROTECTION
Floor height 0" to 6-1/2"
(6 to 165mm) below Insert Base
Floor height greater thant 6-1/2"
(165mm) below Insert Base
See Alternative Floor Protection Worksheet on page 31
*
WARNING
Fire Risk.
Do NOT operate appliance with the
Mantel Heat Deflector removed when
used for clearance reduction.
Failure to comply may cause house fire.
WARNING
Fire Risk.
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having juris-
diction
Page 0
USA and Canada
A
B
C
21.5" (546)
n/a
n/a
n/a
1" (787)
22" (559)
n/a
21" (5)
21" (5)
USA
Canada
E
F
E
18"
8"
18" (457)
16"
8"
18" (457)
USA and Canada
See Figure 31.1
1-1/2 inch (8) of k = 0.49, R = .06
See Figure 31.2
1 inch (25) of k = 0.49, R = 2.04
Maximum Mantel Depth - 12" (305mm)
D
15" (81)
n/a
n/a
A
F
12" (05)
12" (05)
In Canada a full length 6 inch (152mm) S635 flue liner
required as per ULC S628.
In USA a minimum 5 ft length (1.82m), 6 inch (152mm)
diameter flue liner is required as per UL 1482.
Figure 30.1
7044-140B
Mantel
B
Fascia or Trim
C
Insert
D
Fuel Door
E
F

Hearth Extension

Mantel
Optional
21 in.
Mantel
(533mm)
Deflector
February 10, 2010