Section 5. Initial Testing And Checking Of Alarm; Section 6. Interconnecting - Kidde 1SF23/9HI Installer's Manual

Smoke and heat alarm
Hide thumbs Also See for 1SF23/9HI:
Table of Contents

Advertisement

Battery Changing
Loose battery models (battery charging) See section 12
Reconnect mains supply and check green L.E.D. is lit – red L.E.D. will flash
intermittently.
GREEN LED
6. Initial Testing and Checking of Alarm
Having energised circuit, press and hold the test button again – the alarm
should sound and other interconnected ones also, within a few seconds.
Do this for all alarms.
If any do not sound, isolate mains and recheck cabling.
On optical alarms if the red L.E.D. blinks every 30-40 seconds and the alarm
chirps inbetween, it indicates failure of the sensing chamber - replace alarm.
{This condition also exists if the Hush button is pushed}
Advise the house-holder (if present) as to how to test the alarms.
7. Interconnecting
You may interconnect up to 23 Kidde Fyrnetics AC smoke, heat or CO alarms to
this unit. i.e. 24 in total.
Crossing line and neutral connections or line and interconnect connections will
fatally damage all interconnected alarms invalidating the guarantee.
All interconnected alarms must be powered off the same fuse/circuit breaker.
Total cable length between alarms must not exceed 250m (273yds) and be 1.0mm
in diameter, 3 core and earth (BS6243Y). Wiring must conform to the
IEE regulations - BS7671, or latest edition.