Battery Changing
•
Loose battery models (battery charging) See section 12
•
Reconnect mains supply and check green L.E.D. is lit – red L.E.D. will flash
intermittently.
GREEN LED
6. Initial Testing and Checking of Alarm
•
Having energised circuit, press and hold the test button again – the alarm
should sound and other interconnected ones also, within a few seconds.
•
Do this for all alarms.
•
If any do not sound, isolate mains and recheck cabling.
•
On optical alarms if the red L.E.D. blinks every 30-40 seconds and the alarm
chirps inbetween, it indicates failure of the sensing chamber - replace alarm.
{This condition also exists if the Hush button is pushed}
•
Advise the house-holder (if present) as to how to test the alarms.
7. Interconnecting
•
You may interconnect up to 23 Kidde Fyrnetics AC smoke, heat or CO alarms to
this unit. i.e. 24 in total.
•
Crossing line and neutral connections or line and interconnect connections will
fatally damage all interconnected alarms invalidating the guarantee.
•
All interconnected alarms must be powered off the same fuse/circuit breaker.
Total cable length between alarms must not exceed 250m (273yds) and be 1.0mm
in diameter, 3 core and earth (BS6243Y). Wiring must conform to the
IEE regulations - BS7671, or latest edition.
5
RED LED