Maintenance And Testing; Specifications; Regulatory Information - Kidde DM3000 Installation Sheet

Intelligent addressable manual call point
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

Maintenance and testing

Maintenance
Inspect the unit regularly to ensure that it is free from dust and
physical damage. Do not modify internal wiring or circuitry.
Testing
To activate an alarm, push the resettable element or turn the
key clockwise (one click). To reset the device, turn the key
anticlockwise (one click). Reset the control panel after testing.
Replacing the resettable element
Replace the resettable element (or add the breakable element)
as follows:
1.
Unlock and remove the front cover as described in
"Installation" on page 2.
2.
Push the element up, and then pull it out (see Figure 5).
3.
Replace the resettable element (or add the breakable
element, if required).
4.
Replace the front cover.

Specifications

Electrical
Operating voltage
Current consumption
Standby
Alarm
Mechanical and environmental
IP rating
Backbox cable knockouts
Back
Top
Bottom
Wire diameter (terminal block)
Minimum
Maximum
Operating environment
Operating temperature
Storage temperature
Relative humidity
Colour
DM3000
DM3000U
DM3000G
DM3000O
DM3000W
DM3000Y
Weight
Without backbox
With backbox [1]
Dimensions
Without backbox
With backbox [1]
[1] Backbox not supplied
P/N 03-0210-501-0000-01 • ISS 06MAY19
16 to 42 VDC
200 µA
2.9 mA
IP41
1 × Ø 20 mm
1 × Ø 25 mm
2 × Ø 20 mm
0.404 mm (26 AWG)
2.05 mm (12 AWG)
−25 to +72°C
−25 to +72°C
10 to 95% (noncondensing)
Red (RAL3028)
Blue (RAL5005)
Green (RAL6024)
Orange (RAL2008)
White (RAL9003)
Yellow (RAL1003)
110 g
170 g
87 × 87× 26 mm
87 × 87× 57 mm

Regulatory information

This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at https://firesecurityproducts.com).
EU compliance
Certification body
Manufacturer
Year of first CE marking
Declaration of Performance
number [1]
EN 54
Product identification [1]
Intended use
Declared performance
European Union directives
[1] The Declaration of Performance only covers the red manual call
points.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
0370
United Technologies Safety Systems,
80 Changjiang East Road,
QETDZ, Qinhuangdao, Hebei, China
066004.
Authorized EU manufacturing
representative:
UTC Fire & Security B.V. Kelvinstraat
7, 6003 DH Weert, Netherlands.
2019
03-0210-360-1000
EN 54-11 Type A (Indoor Use)
DM3000, DM3000S06, DM3000S18,
DM3000S27
See the product Declaration of
Performance
See the product Declaration of
Performance
2014/53/EU (Radio Equipment
Directive): Hereby, UTC Fire &
Security declares that this device is in
compliance with the essential
requirements and other relevant
provisions of Directive 2014/53/EU.
2012/19/EU (WEEE Directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at
designated collection points. For
more information see:
http://www.recyclethis.info.
3 / 17

Advertisement

Table of Contents
loading

Table of Contents