Analog Inputs to Drive
BACnet
REFERENCE NAME
bus_ref_#
bus_feedback_#
bus_feedback_2_#
NOTE: # symbol represents drive ID number.
Bus reference. When the drive is set for open loop operation in
parameter 100, the bus reference is the speed command to the
drive. In closed loop operation, bus reference is the drive’s
setpoint.
Drive Settings
BACnet
REFERENCE NAM E
vlt6000_reset_counter_#
vlt6000_active_setup_#
vlt2800_prop_gain_#
vlt2800_int_tim e_#
vlt2800_fb_filter_tim e_#
warn_feedback_low_#
warn_feedback_high_#
setpoint_1_#
setpoint_2_#
vlt6000_prop_gain_#
vlt6000_int_tim e_#
vlt6000_fb_filter_tim e_#
NOTE: # symbol represents drive ID number.
old
The values in
are
default values.
DESCRIPTION
Drive speed command
(open loop) or setpoint
(closed loop) via the
serial bus.
Drive feedback value
via the serial bus.
Second drive feedback
value via the serial bus
available in the
VLT 6000 only.
Bus feedback. This is the feedback signal provided to the drive
via the BACnet bus. The VLT 6000 can regulate two feedback
signals provided to the drive.
Range. Percentage of range between minimum reference
(parameter 204) and maximum reference (parameter 205).
DESCRIPTION
Resets kW h counter
(for VLT 6000 only)
Selects active setup
(for VLT 6000 only)
PID proportional gain
(for VLT 2800 only)
PID integration tim e
(for VLT 2800 only)
Feedback filter tim e
(for VLT 2800 only)
W arning low feedback
(for VLT 6000 only)
W arning high feedback
(for VLT 6000 only)
Set point 1
(for VLT 6000 only)
Set point 2
(for VLT 6000 only)
PID proportional gain
(for VLT 6000 only)
PID integration tim e
(for VLT 6000 only)
Feedback filter tim e
(for VLT 6000 only)
Appendix
VLT 6000
RANGE
PARA No.
0% to 100%
N/A
0% to 100%
535
0% to 100%
536
VLT 6000
RANG E
PARA NO.
0=no rest
1=reset
1 to 4
0.00 to10.00
VLT 2800
0.01 to
VLT 2800
9999.00 sec.
0.01 to10.00
VLT 2800
sec.
-999,999.999
to FB high
FB low to
999,999.999
Min. FB to
m ax. FB
Min. FB to
m ax. FB
0.00 to10.00
0.01 to
9999.00 sec.
0.01 to10.00
sec.
VLT is a registered Danfoss trademark
VLT 2800
PARA No.
N/A
535
VLT 6000
only
VLT 2800
PARA NO.
618
VLT 6000
only
002
VLT 6000
only
440
only
441
only
444
only
227
VLT 6000
only
228
VLT 6000
only
418
VLT 6000
only
419
VLT 6000
only
423
VLT 6000
only
424
VLT 6000
only
427
VLT 6000
only
19