Blade bay
Description of installed device
1
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-31X
2
SCSI Storage Expansion Unit
3
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-31X
4
SCSI Storage Expansion Unit
5
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-31X
6
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-31X
Total
Result:
•
7.2 IBM power units < 7.4 IBM power units
•
Two 1200 W power modules will provide full power redundancy for power domain A
Power domain B worksheet (for power modules 3 and 4)
Blade bay
Description of installed device
7
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-N1X
8
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-N1X
9
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-N1X
10
3.06 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-N1X
11
3.2 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-G1X
12
2.8 GHz/400 MHz HS40 blade server with 4 microprocessors - first bay (HS40
occupies 2 bays) 8832-41X
13
2.8 GHz/400 MHz HS40 blade server with 4 microprocessors - second bay (HS40
occupies 2 bays) 8839-41X
14
3.2 GHz/533 MHz HS20 blade server with 2 microprocessors 8832-G1X
Total
Result:
•
14.0 IBM power units > 13.4 IBM power units
•
Two 2000 W power modules will provide full power redundancy for power domain B
Attention: To maintain proper system cooling, each unoccupied blade bay must contain a filler blade. To
maintain proper module cooling, each unoccupied I/O, management-module, or power-module bay must
contain a filler module. An installed power module must be powered on and must not be used as a filler
module.
®
Appendix F. BladeCenter
power module upgrade guidelines
IBM power units
1.6
0.4
1.6
0.4
1.6
1.6
7.2
IBM power units
1.9
1.9
1.9
1.9
1.65
1.55
1.55
1.65
14.0
533