Country-specific considerations: USA, Canada, parts of Latin America,
Taiwan
Power Cables:
(1) Device to Rack PDU or Enterprise C13 PDU power cable
IEC C13 to C14, 10/15a cable
typical: 36L8886 (2.8m)
requirement: C14 plug, long enough to reach
available option: 94G7448 (14ft)
(2) Rack PDU to wall line cord
IEC C19 to country-specific connector, 16/20a, 14ft (4.3m)
(3) Rack PDU to UPS power cable
IEC C19 to C20, 16/20a
00N7700 (2m)
provided with 37L6861 APC SU-5000RMB
(4) Rack PDU to Front-end PDU power cable
IEC C19 to C20, 16/20a
00N7698 (1m) provided with the NetBAY Front-end PDUs
00N7700 (2m) provided with the DPI Front-end PDUs
(5) Front-end PDU to wall line cord
hardwired to country-specific connector, 30/32a, 60/63a, 8.2ft
(2.5m)
(7) Device to High Density PDU power cable
IEC C19 to C20, 16/20a, 2.5m
(8) Enterprise PDU to wall line cord
hardwired or pluggable to country-specific connector, 30/60a, 14ft
(4.3m)
(9) High Density PDU to wall line cord
hardwired or plugugable to country-specific connector, 60a, 8.2ft
(2.5m)
(10) Device to FE-, E-, or HD-PDU power cable
IEC C13 to C20, 10/15a cable
option: 23K4809 9ft (2.8m)
Power Load Capacity
(2) Line Cords: Rack PDU
(5) Line Cords: Front-end
PDU
(8) Line Cords:Enterprise PDU
(9) Line Cords:High Density PDU
Rack PDUs
Part
Plug Type
Source Circuit
Number
(single phase 50/60Hz)
32P1761
NEMA L5-15
P
100-127Vac,
32P1736
NEMA L5-20P
100-127Vac, 20a
NEMA L6-20P
200-240Vac, 20a
Front-end PDUs
Part
Plug Type
Source Circuit (50/60Hz)
Number
32P1751 NEMA L5-30P
100-127Vac, 30a,
single-phase
32P1766 NEMA L6-30P
208Vac, 30a, single-phase
line-to-line with ground
32P1767 IEC 309-2P+G
208Vac, 60a, single-phase
line-to-line with ground
Enterprise PDUs
Part
Plug Type
Source Circuit (50/60Hz)
Number
46 NEMA L6-30P
208Vac, 30a, single-phase
26K42
dedicated circuit
26K4242 IEC 309 2P+G
208Vac, 60a, single-phase
dedicated circuit
26K4244 IEC 309 3P+G
208Vac, 60a, three-phase
delta dedicated circuit
26K4256 IEC 309 2P+G
208Vac, 60a, single-phase
dedicated circuit
26K4258 IEC 309 3P+G
208Vac, 60a, three-phase
delta dedicated circuit
High Density PDUs
Part
Plug Type
Source Circuit (50/60Hz)
Number
73P5855 IEC 309 2P+G
208Vac, 60a, single-phase
dedicated circuit
73P5847 IEC 309 3P+G
208Vac, 60a, three-phase
delta dedicated circuit
Chapter 55. xSeries rack power configurator
PDU Output
(single phase 50/60Hz)
15a
six 100-127Vac, NEMA 5-15R
receptacles, shared
12a
seven 100-127Vac, shared 15a
seven 200-240Vac, shared 15a
PDU Output
(single phase 50/60Hz)
three 100-127Vac, 20a each, shared
24a
three 208Vac, 20a each, share
d 24a
three 208Vac, 20a each, shared
48a
PDU Output
(single phase 50/60Hz)
twelve 208Vac, 10a each, shared
24a
twelve 208Vac, 10a each, shared
48a
twelve 208Vac, 10a each, shared
28a per four outlet phase group
six 208Vac, 16a each, shared 48a
six 208Vac, 16a each, shared 28a
per two outlet phase group
PDU Output
(single phase 50/60Hz)
twelve 208Vac, 16a each, shared
48a
twelve 208Vac, 16a each, shared
28a per four outlet phase group
481