Battery Replacement Procedure - CyberPower CP900EPFCLCD User Manual

Ups system
Hide thumbs Also See for CP900EPFCLCD:
Table of Contents

Advertisement

3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source
of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL
SHOCK! The likelihood of such shock will be reduced if such grounds are removed during
installation and maintenance (applicable to a UPS and a remote battery supply not having a
grounded circuit)

BATTERY REPLACEMENT PROCEDURE:

1. Turn off and unplug all connected equipment.
2. Turn the UPS off and unplug it from the AC power source.
3. Turn the UPS on its side.
4. Remove the retaining screw located on the bottom of the UPS.
5. Slide the battery compartment cover completely off of the unit.
6. Remove the batteries from the compartment.
7. Disconnect the battery wires from the batteries.
8. CP900/1300EPFCLCD: Install the replacement batteries by connecting the red wire (+) and black
wire (-) to the same color connectors from the battery pack.
CP1500EPFCLCD: Install the replacement batteries by connecting the wire bundle (composed of one
red wire and one black wire) to the connector from the battery pack.
9. Put the batteries back into the compartment.
10. Slide back the battery compartment cover and tighten the retaining screw.
11. Recharge the UPS for 8-16 hours to fully charge the battery.
REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly.
Almost any retailer that sells lead-acid batteries collects used batteries for recycling.