CP900/1300/1500EPFCLCD
User's Manual
K01-0000331-00

Advertisement

Table of Contents
loading

Summary of Contents for CyberPower CP900EPFCLCD

  • Page 1 CP900/1300/1500EPFCLCD User’s Manual K01-0000331-00...
  • Page 2: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS. CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection.
  • Page 3: Basic Operation

    CP1300/1500EPFCLCD. 2.Ensure that the equipment plugged into the battery power-supplied/surge outlets does not exceed the UPS unit's rated capacity ( 900VA/540W for CP900EPFCLCD; 1300VA/780W for CP1300EPFCLCD; 1500VA/900W for CP1500EPFCLCD). If the rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.
  • Page 4: Hardware Installation Guide

    menu. Holding the switch for more than 2 seconds will silence the buzzer. 6. Control Switch Press the Control switch for 3 seconds in AC/Utility Power Mode to perform a Self Test of the battery. 7. USB Power Ports The USB Power ports provide 5V 1A power output. 8.
  • Page 5: Battery Replacement

    5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc. Avoid using extension cords. 6.
  • Page 6: Battery Replacement Procedure

    10. Slide back the battery compartment cover and tighten the retaining screw. 11. Recharge the UPS for 8-16 hours to fully charge the battery. REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Almost any retailer that sells lead-acid batteries collects used batteries for recycling. CP900EPFCLCD CP1300EPFCLCD CP1500EPFCLCD...
  • Page 7: Definitions For Illuminated Lcd Indicators

    DEFINITIONS FOR ILLUMINATED LCD INDICATORS ONLINE: The UPS is supplying utility power to connected equipment. BATTERY: During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a pause) to indicate the UPS is operating from its internal batteries. During a prolonged brownout or blackout, the alarm will beep rapidly every 1/2 second (and the BATT.CAPACITY meter shows one 20% capacity...
  • Page 8: Technical Specifications

    AC line voltage without using battery power. This is a normal, automatic operation of your UPS, and no action is required on your part. For more information about functions setup, please refer to the Function Setup Guide. TECHNICAL SPECIFICATIONS Model CP900EPFCLCD CP1300EPFCLCD CP1500EPFCLCD Capacity (VA) 900VA/540W...
  • Page 9: Troubleshooting

    Typical Recharge Time 8 hours Charging Current(Max.) 0.6A User Replaceable Status Indicators Indicators Power On, LCD Display Audible Alarms On Battery, Low Battery, Overload Communication ® PowerPanel Personal Windows 8 / 7/ Vista / XP, and Server 2012 / 2008 / 2003, Linux Edition Software Management Auto-Charger...
  • Page 10 CyberPower Systems (USA),Inc .

This manual is also suitable for:

Cp1300epfclcdCp1500epfclcd