Carel µC2SE User Manual page 29

Electronic control
Hide thumbs Also See for µC2SE:
Table of Contents

Advertisement

4.3.8 Unit setting parameters (H*)
display
parameter and description
indicat.
H01
Unit model
0= air_air unit
1= air_air heat pump
2= air_water chiller
3= air_water heat pump
4= water_water chiller
5= water_water heat pump with reversal on gas circuit
6= water_water heat pump with reversal on water circuit
7= condensing unit
8= reverse-cycle condensing unit
9= water-cooled condensing unit
10= reverse-cycle water-cooled condensing unit
11= cooling only air-air unit with electric heaters
H02
Number of condensers
0=1 circuit
1=2 circuits
H03
Number of evaporators
0=1 evaporator
1=2 evaporators
H04
Number of compressors per circuit
0=1 comp. ON 1 circuit (single circuit)
1=2 comp. in tandem ON 1 circuit (single circuit)
2=1 comp. per circuit, 2 circuits (two circuits)
3=2 comp. in Tandem, 2 circuits (two circuits)
4=1 compressor and 1 Capacity step in one circuit
5=1 compressor and 1 capacity Step per circuit
H05
Pump/outlet fan (Air/Air) mode (output N2)
0= absent
1= always ON
2= ON upon request of the controller
3= ON upon request of the controller and for set time
4= follow hot keep or hot start in heating, always on in cooling
5= follow hot keep or hot start in heating, follow the comp. in cooling
H06
Cooling/Heating digital input
0= absent
1= present
H07
ON/OFF digital input
0= absent
1= present
2
H08
µC
SE
network confi guration
2
0=
µC
SE
only
µC
2
SE
1=
+ valve
µC
2
SE
2=
+ exp.
3= µC2SE + exp. + valve1 + valve2
4= µC2SE + exp. + valve1
H09
Lock keypad
0= disabled
1= enabled
H10
Serial address
0= future use as terminal
H11
Output modes (see Table 5.3 and following pag. 56)
H12
Capacity-control and reversing valve logic
0= Both normally closed
1= Both normally open
2= Inversion valve normally open and capacity-control valve normally closed
3= Inversion valve normally closed and capacity-control valve normally open
H13
Activate pump down
H14
Minimum pump down pressure
H15
Maximum pump down time
H16
Activate autotuning
H17
Minimum DTE value allowed
H18
Maximum DTE value allowed
H19
Maximum DTC value allowed
H21
Second pump function
0= Disabled
1= Backup and weekly rotation
2= Backup and daily rotation
3= Condensing control on corresponding set point
4= Condensing control always on
H22
Disable load default values
0= Function disabled
1= Function enabled
H23
Enable Modbus
®
µC
2
SE - +030220426 - rel. 2.0 - 03.08.2009
default
min.
max.
U.O.M. variat.
level
F
0
11
Flag
1
U
0
1
Flag
1
F
0
1
Flag
1
F
0
5
Flag
1
F
0
5
Flag
1
U
0
1
Flag
1
U
0
1
Flag
1
F
0
3
Flag
1
U
0
1
Flag
1
U
1
200
-
-
F
0
12
Int
1
F
0
3
Flag
1
F
0
1
-
1
F
0
500
Dbar
0.1
F
0
180
s
1
F
0
1
Flag
1
F
0.0
1760
°C/°F
0.1
F
0.0
1760
°C/°F
0.1
F
0.0
1760
°C/°F
0.1
F
0
4
int
1
F
0
1
Flag
1
F
0
1
Flag
1
29
def.
visibility supervis.
Modbus
variable
2
-
54 (R/W)
261
0
F
12 (R/W)
12
0
-
13 (R/W)
13
0
-
55 (R/W)
262
1
-
56 (R/W)
263
0
-
14 (R/W)
14
0
-
15 (R/W)
15
0
-
57 (R/W)
264
1
-
16 (R/W)
16
1
-
58 (R/W)
265
0
-
59 (R/W)
266
1
-
60 (R/W)
267
0
V
17 (R/W)
17
20
M
37(R/W)
37
30
M
61 (R/W)
268
0
-
22 (R/W)
22
0
-
68 (R/W)
68
800
-
69 (R/W)
69
800
-
70 (R/W)
70
0
-
62 (R/W)
269
0
-
18 (R/W)
18
0
-
11 (R/W)
11
variable
type
Integer
Digital
Digital
Integer
Integer
Digital
Digital
Integer
Digital
Integer
Integer
Integer
Digital
Analog
Integer
Digital
Analog
Analog
Analog
Integer
Digital
Digital
Table 4.h