Adaptive Recovery - Jackson Systems Comfort System T-32-P Installation Manual

Universal thermostat
Hide thumbs Also See for Comfort System T-32-P:
Table of Contents

Advertisement

TESTING
Press the
MODE
button until Mode
setpoint a few degrees below the space temperature. The cooling and fan relays will energize and the
word
Cool
will change to
lower the setpoint further and the second stage cooling relay will energize. A period ( ) will be
displayed after the word
TESTING HEAT PUMP OPERATION
When the T-32-P is configured for heat pump operation, testing is the same as for a conventional
heating and cooling system with the exception that the fan relay is energized on a call for both
heating and cooling. Emergency Heat mode is only active when the thermostat MODE button is set to
emergency heat.
E. Heat
will be displayed on the LCD.
When the thermostat is in the heat pump mode, the reversing valve is energized with a cooling call
'O' or heating call 'B', it will remain energized until there is an opposite call. If after 30 minutes there is
no call, the reversing valve will de-energize.
RESETTING THE TIME DELAYS
After testing the thermostat, change CD=1 to CD=0 in the Advanced Installer menu. This will be
confirmed when the flashing wrench icon no longer appears on the LCD.
FACTORY TEST MODE
The T-32-P contains a simple factory Test Mode that can confirm relay outputs, slide switch
configuration along with a factory default reset.
TS=0 - Factory Test Mode is OFF
TS=1 - Displays system configuration code based on slide switch settings
(for factory use only).
TS=2 - Cycles each relay on and off in an endless loop.
be disabled when performing this test
TS=3 - Resets software to factory defaults. Press

ADAPTIVE RECOVERY

Adaptive Recovery is only available in programmable mode (Sw6=ON and OS=1). The Adaptive
Recovery function of the T-32-P permits the user to program a time that a desired set temperature is
required. The thermostat then calculates the most energy efficient time to bring on the equipment to
reach the setpoint at the designated time. This calculation involves a complex control algorithm that
compares the space temperature deviation from setpoint and rate of recovery history. "RECO"
flashes on the LCD when Adaptive Recovery is active.
Cool
appears on the LCD. Use the ( ) button and lower the
Cooling
. If the thermostat has been configured for multi-stage operation,
Mode
.
will be displayed on the LCD. When the W2 relay is energized
Equipment should
.
Fan
button to initiate.
.
E. Heating
14