ADVANCED INSTALLER SETTINGS MENU
Symbol
Default
HL
90
CL
50
CF
F
C1
0.0
TC
12
AH
2
FO
0
4 schedules per day = constant fan
in 1, 2, 3 and auto fan in 4
2 schedules per day = constant fan
in Day and auto fan in Night
FP
0
FN
- - -
TT
OFF
OS
1
HB
OFF
LB
OFF
AD
1
Maximum Heating Setpoint Limit
Adjustable from 41° F - 120° F
Minimum Cooling Setpoint Limit
Adjustable from 43° F - 122°
Temperature Display
CF=F - Fahrenheit
CF=C - Celsius
Internal Sensor Calibration
Adjustable +/- 9° F in 0.2
Time Format
TC=12 - 12 Hour Time
TC=24 - Military Time
TC=00 - No time displayed in non-programmable mode
Temporary Hold Time for Programmable Mode
0.5 - 12 hours or OFF which holds to next event
Advanced Fan Function
FO=0 - No advanced fan function
FO=2 - Constant fan during occupied mode.
(Fan must be set to ON for this function to work)
Fan Purge
Adjustable from 0 - 5 minutes after any call
Mode
FN=
- - -
Manual Changeover
FN=A - Auto Changeover
FN=C - Cooling Only
FN=H - Heating Only
Remote Sensor
TT=OFF - No Remote Sensor
TT=OA - Outdoor Sensor
TT=RS - Remote Indoor Sensor
TT=AU - Indoor Remote Sensor Averaging with
Internal Sensor
Adaptive Recovery (Programmable Mode)
OS=0 - OFF
OS=1 - ON
High Balance Point
Adjustable from OFF to 32° F - 122° F
Low Balance Point
Adjustable from OFF to 14° F - 77° F
Modbus Address
Adjustable from 1 - 99
Function
° F increments