1. Nominal 350 CFM/ton cooling airflow is delivered with SW1--5 and SW4--3 set to OFF.
Set SW1--5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4--3 to ON for nominal 325 CFM/ton (--7% airflow).
Set both SW1--5 and SW4--3 to ON for nominal 370 CFM/ton (+7% airflow).
The above adjustments in airflow are subject to motor horsepower range/capacity.
2. Maximum cooling airflow is achieved when switches SW2--1, SW2--2, SW2--3 and SW1--5 are set to ON, and SW4--3 is set to OFF.
3. All heating CFM's are when low/medium heat rise adjustment switch (SW1--3) and comfort/efficiency adjustment switch (SW1--4) are both
set to OFF.
4. Ductwork must be sized for high--heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not
recommended because high--heat operation will be above 1.0 ESP.
5. All airflows on 21" casing size furnaces are 5% less on side return only installations.
6. Return air above 1800 CFM on 24.5" casing sizes requires two sides, one side and bottom or bottom only , to allow sufficient airflow to the furnace.