Sequence Of Operation - Carrier 59MN7A Installation, Start-Up, Operating And Service And Maintenance Instructions

Modulating 4-way multipoise condensing gas furnace series 200
Table of Contents

Advertisement

SEQUENCE OF OPERATION

CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation.
Furnace control must be grounded for proper operation or
control will lock out.
Control is grounded through
green/yellow wire routed to gas valve and burner box
screw.
Using the schematic diagram, follow the sequence of operation
through the different modes. See Fig.
wiring diagram very carefully!!
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1-and-W2), the control will start a 90-second
blower-only ON period two seconds after power is restored, if the
thermostat is still calling for gas heating. The amber LED light will
flash code 12 during the 90-second period, after which the LED
will be ON continuous, as long as no faults are detected. After the
90-second period, the furnace will respond to the thermostat
normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot surface igniter HSI, and gas valve GV.
Communicating Control and Modulating Heating
(Adaptive Mode)
Best comfort will be attained when a communicating wall control
is used with this product. Wiring and set- -up instructions are
provided with the communicating control. See the furnace data
sheet accessory section for help in selecting the appropriate
communicating control for this furnace.
When a communicating control is used, the furnace will modulate
through its full operation range, or can be limited via the minimum
and maximum cfm configurations.
Operation of the furnace at the beginning and end of each heating
cycle will be the same as detailed below in the Single- -Stage
Thermostat section EXCEPT that the communicating control will
send modulating rate command signals through the communication
bus rather than energizing the 24- -v thermostat terminals. Note that
the R to W/W1 circuit signal will be controlled by the COMMR
relay on the furnace control. See the wiring diagram in Fig. 65 .
Single-Stage Thermostat and Modulating Heating
(Adaptive Mode)
See Fig. 34 and 35 for thermostat connections.
NOTE:
Minimum-heat only switch SW1-2 selects the
minimum-heat only operation mode when ON. Intermediate-heat
only switch SW4-2 selects intermediate-heat only operation
mode when ON. If both switches are ON the furnace control will
default to intermediate-heat. If either or both switches are ON, the
furnace control will operate at two-stages only as referenced in
Two Stage Thermostat section below. If both switches are OFF the
furnace control will operate in the adaptive heating mode in
response to a call for heat. See Fig. 56. When the W2 thermostat
terminal is energized it will always cause maximum-heat operation
as long as the R to W circuit is closed, regardless of the setting of
the minimum-heat or intermediate-heat only switches.
This furnace can operate as a modulating furnace with a
single-stage thermostat because the furnace control CPU includes a
programmed adaptive sequence of controlled operation, which
selects a modulated rate between minimum- and
65
. Read and follow the
maximum-heat.
This selection is based upon the stored history of the length of
previous gas-heating periods of the single-stage thermostat.
The furnace will start up in either intermediate-, or maximum-heat.
The furnace will transition and operate at minimum-heat or the
calculated modulating rate after starting and operating for 45
seconds at intermediate-heat. The furnace control CPU defaults to
minimum-heat on the first thermostat cycle and calculates the
modulating rate that the furnace should run at for 19 minutes on
subsequent heat cycles.
If the power is interrupted, the stored modulating rate is erased and
the furnace control will select intermediate-heat for 45 seconds,
minimum-heat for 19 minutes and then switch to maximum-heat,
as long as the thermostat continues to call for heat. The furnace
control CPU then uses this information to calculate the modulating
rate the furnace will operate at on the next heating cycle. If the
calculated modulating rate is between 40% - 99% then the furnace
control CPU will operate for 45 seconds at intermediate-heat, and
then operate at the calculated modulating rate for up to 19 minutes
and then switch to maximum-heat as long as the thermostat
continues to call for heat. If the calculated modulating rate is 100%
then the furnace control will only operate at maximum-heat until
the thermostat is satisfied.
The wall thermostat "calls for heat", closing the R to W circuit. The
furnace control CPU performs a self-check, verifies the low,
medium, and high pressure switch contacts LPS,MPS, and HPS are
open, then de-energizes the PSR relay to close the NC contact.
1. Inducer Prepurge Period - The furnace control CPU turns
on inducer motor IDM and slowly increases the inducer
motor speed. After the low pressure switch LPS closes the
furnace control CPU continues to increase the inducer mo-
tor speed until the medium pressure switch MPS closes.
When the medium pressure switch MPS closes, inducer mo-
tor RPM is noted by the furnace control CPU, and a
25-second prepurge period begins. The RPM is used to
evaluate vent system resistance.
used to determine the required RPM necessary to operate
the inducer motor during pre-purge, the first 45 seconds of
intermediate-heat, or any modulating rate that the furnace
will transition to after the blower on-delay is completed.
NOTE:
The heat cycle can start in either intermediate- or
maximum-heat. If a maximum-heat cycle is initiated, the furnace
control CPU will continue to increase the inducer motor speed
after the medium pressure switch MPS closes. When the medium
pressure switch closes, inducer motor RPM is noted by the furnace
control CPU, and a 25-second prepurge period begins. The RPM
is used to evaluate vent system restriction. This evaluation is then
used to determine the required RPM necessary to operate the
inducer motor in maximum-heat pre-purge, or maximum-heat.
The high pressure switch HPS should be closed before ignition but
the furnace control ignores this input until after ignition occurs.
2. Igniter Warm-Up - At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second ig-
niter warm-up period
3. Trial-For-Ignition Sequence - When the igniter warm-up
period is completed the main gas valve relay contact GVR
closes to energize the gas valve solenoid GV (pin 5). The
gas valve solenoid GV (pin 5) permits gas flow to the burn-
ers where it is ignited. Five seconds after the GVR closes, a
2-second Flame-Proving period begins. The HSI igniter
will remain energized until flame is sensed or until the
2-second flame proving period begins.
4. Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control
CPU begins the blower-ON delay period and continues to
hold the gas valve GV (pin 5) open. If the burner flame is
not proved within two seconds, the furnace control CPU
will close the gas valve GV (pin 5), and the furnace control
92
This evaluation is then

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

59tp6a series 2

Table of Contents