c.
From the "3 Communications" display, select "1 Port Functions" and configure COM1 for
"Automation" and parallel port for "Auto Bkp Prn."
Note: If a serial printer is being used as a automation backup printer, congigure COM2 as the "Auto
Bkp Prn" instead of the parallel port.
d. From "4 System Options" select "MstrAuto" and set appropriate "Rcvr ID."
e. From "6 Slave List" enter a unique Slave number for each slave receiver.
f.
Exit the programming mode and cycle power on the Master Receiver for the new settings to take
effect.
2. Program the Slave (SlvAuto) Receiver as follows:
a. Power up the Slave Receiver and allow the Line Cards to be initialized.
b. From the "Installer/Program Menu/General Options" display, select "1 Operation Mode" and
configure for "Automatic."
c.
From "4 System Options" select verify "SlvAuto" setting and set appropriate "Rcvr ID." matching the
number programmed in the Master Receiver.
d. Exit the programming mode.
e. Repeat a. through d. on the second Slave Receiver, if being used.
3. Using 4-pin RJ-11 cables, connect a cable from the Master Receiver to the first Slave Receiver and then
connect a second cable from the first Slave Receiver to the second Slave Receiver.