OVATION 214

HEATER SETTINGS

The controller can control up to two heating stages. Set internal
switch #6 to OFF to use on heating stage; set it to "ON" to use both
heating stages.
CASCADING HEATERS
When cascading heating is used, the operation of heating stages is
based on the average room temperature (internal switch #8 is OFF).
HEATING
OUTPUTS
HEATER 2
HEATER 1
If the room temperature rises:
- at Set Point - Heater 1 Offset - Heater 1 Differential: Heater 2
turns off.
- at Set Point - Heater 1 Offset: Heater 1 turns off.
If the room temperature falls:
- at Set Point - Heater 1 Offset - Heater 1 Differential: Heater 1
turns on.
- at Set Point - Heater 1 Offset - Heater 1 Differential - Heater 2
Differential: Heater 2 turns on.
48
OVATION 214 rev.00
ON
ON
OFF
HEATER 2
DIFFERENTIAL
HEATER 2
TURNS ON
HEATER 2
TURNS OFF
HEATER 1
TURNS ON
HEATER 1
TURNS OFF
HEATER 1
HEATER 1
DIFFERENTIAL
OFFSET
ROOM T°
SET POINT